Daikin EWWQ090G-SS [14/41] Electrical specifications

Daikin EWWQ090G-SS [14/41] Electrical specifications
ELECTRICAL SPECIFICATIONS
EWWQ G-SS
100
120
130
150
170
210
090
MODEL
Power supply
Phases
---
3
3
3
3
3
3
3
Frequency
Hz
50
50
50
50
50
50
50
Voltage
V
400
400
400
400
400
400
400
Voltage tollerance Minimum
%
-10%
-10%
-10%
-10%
-10%
-10%
-10%
Voltage tollerance Maximum
%
+10%
+10%
+10%
+10%
+10%
+10%
+10%
Unit
Maximum starting current
A
204
255
261
308
316
354
466
Nominal running current cooling
A
42
45
48
54
61
68
86
Maximum running current
A
59
66
72
80
88
102
131
Maximum current for wires sizing
A
65
72
79
88
96
112
144
Compressors
Phases
No.
3
3
3
3
3
3
3
Voltage
V
400
400
400
400
400
400
400
Voltage tollerance Minimum
%
-10%
-10%
-10%
-10%
-10%
-10%
-10%
Voltage tollerance Maximum
%
+10%
+10%
+10%
+10%
+10%
+10%
+10%
Maximum running current
A
59
66
72
80
88
102
131
Starting method
---
DOL
DOL
DOL
DOL
DOL
DOL
DOL
EWWQ G-SS
300
360
240
MODEL
Power supply
Phases
---
3
3
3
Frequency
Hz
50
50
50
Voltage
V
400
400
400
Voltage tollerance Minimum
%
-10%
-10%
-10%
Voltage tollerance Maximum
%
+10%
+10%
+10%
Unit
Maximum starting current
A
481
640
677
Nominal running current cooling
A
95
118
143
Maximum running current
A
145
183
221
Maximum current for wires sizing
A
160
201
243
Compressors
Phases
No.
3
3
3
Voltage
V
400
400
400
Voltage tollerance Minimum
%
-10%
-10%
-10%
Voltage tollerance Maximum
%
+10%
+10%
+10%
Maximum running current
A
145
183
221
Starting method
---
DOL
DOL+PW
PW
Fluid: Water
Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%.
Maximum starting current: starting current of biggest compressor + current of the compressor at 75% maximum load
Nominal current in cooling mode is referred to the following conditions: evaporator 12/7°C; condenser 30/35°C; compressors current
Maximum running current is based on max compressor absorbed current in its envelope
Maximum unit current for wires sizing is based on minimum allowed voltage
Maximum current for wires sizing: (compressors full load ampere) x 1,1.