Daikin EWWQ090G-SS [15/41] Electrical specifications

Daikin EWWQ090G-SS [15/41] Electrical specifications
ELECTRICAL SPECIFICATIONS
EWWQ L-SS
205
230
260
290
330
430
180
MODEL
Power supply
Phases
---
3
3
3
3
3
3
3
Frequency
Hz
50
50
50
50
50
50
50
Voltage
V
400
400
400
400
400
400
400
Voltage tollerance Minimum
%
-10%
-10%
-10%
-10%
-10%
-10%
-10%
Voltage tollerance Maximum
%
+10%
+10%
+10%
+10%
+10%
+10%
+10%
Unit
Maximum starting current
A
263
320
333
388
403
456
597
Nominal running current cooling
A
83
89
96
109
121
137
171
Maximum running current
A
118
131
144
160
175
205
262
Maximum current for wires sizing
A
130
144
159
176
193
225
288
Compressors
Phases
No.
3
3
3
3
3
3
3
Voltage
V
400
400
400
400
400
400
400
Voltage tollerance Minimum
%
-10%
-10%
-10%
-10%
-10%
-10%
-10%
Voltage tollerance Maximum
%
+10%
+10%
+10%
+10%
+10%
+10%
+10%
Maximum running current
A
59
59
66
66
72
72
80
80
88
88
102
102
131
131
Starting method
---
DOL
DOL
DOL
DOL
DOL
DOL
DOL
EWWQ L-SS
540
600
660
720
480
MODEL
Power supply
Phases
---
3
3
3
3
3
Frequency
Hz
50
50
50
50
50
Voltage
V
400
400
400
400
400
Voltage tollerance Minimum
%
-10%
-10%
-10%
-10%
-10%
Voltage tollerance Maximum
%
+10%
+10%
+10%
+10%
+10%
Unit
Maximum starting current
A
626
785
822
860
898
Nominal running current cooling
A
189
210
236
260
284
Maximum running current
A
290
328
366
403
441
Maximum current for wires sizing
A
319
361
402
444
485
Compressors
Phases
No.
3
3
3
3
3
Voltage
V
400
400
400
400
400
Voltage tollerance Minimum
%
-10%
-10%
-10%
-10%
-10%
Voltage tollerance Maximum
%
+10%
+10%
+10%
+10%
+10%
Maximum running current
A
145
145
145
183
183
183
183
221
221
221
Starting method
---
DOL
DOL
DOL+PW
DOL+PW
PW
Fluid: Water
Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%.
Maximum starting current: starting current of biggest compressor + current of the compressor at 75% maximum load
Nominal current in cooling mode is referred to the following conditions: evaporator 12/7°C; condenser 30/35°C; compressors current
Maximum running current is based on max compressor absorbed current in its envelope
Maximum unit current for wires sizing is based on minimum allowed voltage
Maximum current for wires sizing: (compressors full load ampere) x 1,1.
Page 15 of 41