Daikin EWYT650B-XSA2 [40/75] Electrical specification

Daikin EWYT235B-XSA2 [40/75] Electrical specification
40 | 75
ELECTRICAL SPECIFICATION
MODEL
EWYT430B-
SSA2
EWYT490B-
SSA2
EWYT540B-
SSA2
EWYT590B-
SSA2
EWYT630B-
SSA2
POWER SUPPLY
No.
3
3
3
3
3
Hz
50
50
50
50
50
V
400
400
400
400
400
%
-10%
-10%
-10%
-10%
-10%
%
10%
10%
10%
10%
10%
UNIT
A
666
712
757
795
825
A
253
291
328
353
372
A
334
379
425
463
493
A
367
417
468
509
542
FANS
A
28
28
28
35
35
COMPRESSORS
No.
3
3
3
3
3
V
400
400
400
400
400
%
-10%
-10%
-10%
-10%
-10%
%
10%
10%
10%
10%
10%
A
301
372
443
447
452
DOL
DOL
DOL
DOL
DOL
EWYT~B-SL
MODEL
EWYT085B-
SLA1
EWYT105B-
SLA1
EWYT135B-
SLA1
EWYT175B-
SLA1
EWYT205B-
SLA2
EWYT215B-
SLA1
POWER SUPPLY
Phases
No.
3
3
3
3
3
3
Frequency
Hz
50
50
50
50
50
50
Voltage
V
400
400
400
400
400
400
Voltage tolerance Minimum
%
-10%
-10%
-10%
-10%
-10%
-10%
Voltage tolerance Maximum
%
10%
10%
10%
10%
10%
10%
UNIT
Maximum inrush current
A
211
327
343
464
408
495
Nominal running current cooling
A
54
66
76
99
125
123
Maximum running current
A
68
85
101
131
166
163
Maximum current for wires sizing
A
75
94
111
144
183
179
FANS
Nominal running current cooling
A
4
6
8
8
10
10
COMPRESSORS
Phases
No.
3
3
3
3
3
3
Voltage
V
400
400
400
400
400
400
Voltage tolerance Minimum
%
-10%
-10%
-10%
-10%
-10%
-10%
Voltage tolerance Maximum
%
10%
10%
10%
10%
10%
10%
Maximum running current
A
64
92
89
146
184
151
Starting method
DOL
DOL
DOL
DOL
DOL
DOL

Содержание

Скачать