ELECTRICAL SPECIFICATION
MODEL
EWYT265B-
XRA2
EWYT310B-
XRA2
EWYT350B-
XRA2
POWER SUPPLY
Phases
No.
3
3
3
Frequency
Hz
50
50
50
Voltage
V
400
400
400
Voltage tolerance Minimum
%
-10%
-10%
-10%
Voltage tolerance Maximum
%
10%
10%
10%
UNIT
Maximum inrush current
A
443
572
606
Nominal running current cooling
A
145
169
192
Maximum running current
A
201
240
274
Maximum current for wires sizing
A
221
264
301
FANS
Nominal running current cooling
A
14
10
11
COMPRESSORS
Phases
No.
3
3
3
Voltage
V
400
400
400
Voltage tolerance Minimum
%
-10%
-10%
-10%
Voltage tolerance Maximum
%
10%
10%
10%
Maximum running current
A
177
235
292
Starting method
DOL
DOL
DOL
EWYT400B-
XRA2
EWYT440B-
XRA2
EWYT500B-
XRA2
EWYT560B-
XRA2
EWYT600B-
XRA2
EWYT630B-
XRA2
EWYT650B-
XRA2
No.
3
3
3
3
3
3
3
Hz
50
50
50
50
50
50
50
V
400
400
400
400
400
400
400
%
-10%
-10%
-10%
-10%
-10%
-10%
-10%
%
10%
10%
10%
10%
10%
10%
10%
A
644
674
728
773
811
841
841
A
214
237
276
315
339
360
353
A
312
342
395
441
479
509
509
A
343
376
435
485
527
560
560
A
14
14
17
17
20
20
32
No.
3
3
3
3
3
3
3
V
400
400
400
400
400
400
400
%
-10%
-10%
-10%
-10%
-10%
-10%
-10%
%
10%
10%
10%
10%
10%
10%
10%
A
297
301
372
443
447
452
452
DOL
DOL
DOL
DOL
DOL
DOL
DOL
Fluid: Water
Allowed voltage tolerance ± 10%, Voltage unbalance between phases must be within ± 3%.
Maximum starting current: In case of inverter driven units, no inrush current at start up is experienced.
Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C;
compressors + fans current
Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current
Maximum unit current for wires sizing is based on minimum allowed voltage
Maximum current for wires sizing: (compressors full load ampere + fans current) x 1,1
The data are referred to the standard unit without options
For the electrical data of the hydronic kit refer to "Options technical data"
All data are subject to change without notice, Please refer to unit nameplate data