Daikin EWYT650B-XRA2 [44/75] Electrical specification

Daikin EWYT630B-XLA2-VFDFAN [44/75] Electrical specification
44 | 75
ELECTRICAL SPECIFICATION
MODEL
EWYT235B-
XSA2
EWYT265B-
XSA2
EWYT310B-
XSA2
EWYT350B-
XSA2
POWER SUPPLY
Phases
3
3
3
3
Frequency
50
50
50
50
Voltage
400
400
400
400
Voltage tolerance Minimum
-10%
-10%
-10%
-10%
Voltage tolerance Maximum
10%
10%
10%
10%
UNIT
Maximum inrush current
429
443
562
594
Nominal running current cooling
132
143
170
192
Maximum running current
186
201
229
262
Maximum current for wires sizing
205
221
252
288
FANS
Nominal running current cooling
15
15
15
17
COMPRESSORS
Phases
3
3
3
3
Voltage
400
400
400
400
Voltage tolerance Minimum
-10%
-10%
-10%
-10%
Voltage tolerance Maximum
10%
10%
10%
10%
Maximum running current
181
177
235
292
Starting method
DOL
DOL
DOL
DOL
MODEL
EWYT400B-
XSA2
EWYT440B-
XSA2
EWYT500B-
XSA2
EWYT560B-
XSA2
EWYT600B-
XSA2
EWYT630B-
XSA2
EWYT650B-
XSA2
POWER SUPPLY
Phases
No.
3
3
3
3
3
3
3
Frequency
Hz
50
50
50
50
50
50
50
Voltage
V
400
400
400
400
400
400
400
Voltage tolerance Minimum
%
-10%
-10%
-10%
-10%
-10%
-10%
-10%
Voltage tolerance
Maximum
%
10%
10%
10%
10%
10%
10%
10%
UNIT
Maximum inrush current
A
629
659
710
755
790
820
841
Nominal running current
cooling
A
215
236
276
313
338
358
361
Maximum running current
A
297
327
377
423
458
488
509
Maximum current for wires
sizing
A
327
360
415
465
504
537
560
FANS
Nominal running current
cooling
A
21
21
25
25
29
29
49
COMPRESSORS
Phases
No.
3
3
3
3
3
3
3
Voltage
V
400
400
400
400
400
400
400
Voltage tolerance Minimum
%
-10%
-10%
-10%
-10%
-10%
-10%
-10%
Voltage tolerance
Maximum
%
10%
10%
10%
10%
10%
10%
10%
Maximum running current
A
297
301
372
443
447
452
452
Starting method
DOL
DOL
DOL
DOL
DOL
DOL
DOL

Содержание