Daikin EWYT650B-XRA2 [68/75] Multiple units installation free field with wind prevalent direction

Daikin EWYT215B-XSA1 [68/75] Multiple units installation free field with wind prevalent direction
INSTALLATIONS NOTES
68 | 75
-
if h < Hc L must at least 3 m for Double V Coil layout units or 1,8m for Parallel Coil layout units
-
if h ≥ Hc or L lower than recommended contact Daikin representative to evaluate possible arrangements
In case two units installed side by side in free filed, the minimum distance recommended between the units is
indicated in the below picture
For mutliple unit installation it is recommended to install the units is a single row as hown in the picture below
For additional information refer to the Installation Manual. If the site does not allow this kind of installation contact
Daikin representative to evaluate possible arrangements.
Multiple units installation free field with wind prevalent direction
Considering an installation in areas with prevailing wind direction (as represented in the first image below):
-
Unit n,1: operates with no air overtemperature
-
Unit n,2: operates in heated environment caused by Unit n,1 and by itself
-
Unit n,3: operates in partially heated environment caused by Unit n,2
To reduce the effect of prevailing wind, it is opportune to set the units main dimension parallel to the wind prevailing
wind (as represented in the second image below).
Unit n.1
Unit n.2
Unit n.3