ESIE11-05 Options
Service Procedure 189
5.2 DTA104A62
5.2.1 General
This option is for:
Demand operation
Low noise demand
5.2.2 Installation
1. Turn OFF the power to the unit.
2. Remove the front panel of the outdoor module(s). (If the module has two front panels (ie.
one each on the left-hand side and right-hand site), remove the panel on the right-hand side
only.)
3. Remove the switch box service panel.
4. Install the external control adaptor inside the switch box of the unit according to the figure
below and following steps.
1. Mount the 4 PCB supports into the switch box.
2. Mount the external control adaptor on top of the PCB supports.
3. Connect the power supply connector to X37A on the PCB outdoor module.
4. Bundle the redundant length portion of the wire with a clamp.
When installed as shown in the figure below, the external control adaptor can execute demand
control and low noise control simultaneously and execute both functions for more than one unit
as well.
1 External control adaptor