Outline of Control (Hydrobox) ESIE11-05
60 Functional Description
6.2 Thermostat Control
Thermo ON/OFF conditions depend on LWT or room temperature regulation.
For LWT control (factory set):
Cooling
Thermo OFF condition:
LWT < LWT set -2 (for 5 min)
LWT < LWT set -b (immediately; b= field setting A-03)
Thermo ON condition:
LWT > LWT set +3,5
Heating
Thermo OFF condition:
LWT > LWT set +2 (for 5 min)
LWT > LWT set +b (immediately; b= field setting A-03)
Thermo ON condition:
LWT < LWT set -3,5