ESIE11-05 Error Codes
Troubleshooting 107
4.2 A6
Troubleshooting
Replace pump.
Is the
pump able to run?
NO
Is their air
in the system?
YES
YES
YES
YES
YES
Rectify.
(R11T, R12T, R21T, R22T).
Open up automatic air purge in the unit.
A field installed air purges.
Temperature is below 5°C and you want to heat up.
The unit is not working in his envelope.
Flow
switch works
properly.
NO
NO
Replace flowswitch.
Does the
unit do a decent
defrost?
NO
- Check refrigerant charge.
- Min water volume.