OPTIONS
OPTIONS
Thanks to the saving on pumping cost, the payback time for the Inverter Kit is approximately one year.
High ambient kit (opt. code 142A) - Opt. incompatibility 99-42-161.
The high ambient kit allows to increase the maximum operating ambient temeperature. Check the unit operating
envelope for more information.
Variable Primary Flow (opt. code 143)
By selecting opt. 143 the chiller can manage the Variable Primary water flow according to the differential pressure
measured in a specific point of the plant, selected by the plant designer. The differential pressure transducer, is
available as option from the factory (opt. code 144). Once installed, the differential pressure transducer must be
connected to the unit. As an alternative the unit controller can receive directly the differential pressure value
from an external BMS communicating with the standards communications protocols (eg. MODBUS).
A bypass line (field supply) needs to be installed which guarantees that at all times the minimum water flow of
the chiller is supplied (refer to the “Operating limit” chapter for indication on minimum water flow). The bypass
valve will be an ON/OFF normally closed valve controlled by the chiller. In case the minimum water flow allowed
is not reached, the chiller will open the bypass line restoring the water flow above the minimum value.
In case of multiple units installations in a primary only plant, to control the pump speed iCM is required.
Master/Slave function does not support primary only chilled water systems with variable flow operation.
Hydronic options summarizing table
Содержание
- Air cooled chiller with scroll compressors 1
- Databook 1
- Ewat b 1
- Features and benefits 2
- Features and benefits 3
- Features and benefits 4
- Features and benefits 5
- Additional information related to f gas regulation eu no 517 2014 of the european parliament and of the council of 16 april 2014 on fluorinated greenhouse gases and repealing regulation ec no 842 2006 6
- Features and benefits 6
- Features and benefits 7
- Features and benefits 8
- Nomenclature 9
- Options 10
- Standard options supplied on basic units 10
- Mechanical options on request 11
- Options 11
- Options 12
- Electrical options on request 13
- Options options 14
- Installation options on request 15
- Options 15
- Other options on request 15
- Ewat b ss l 16
- Technical specification 16
- Ewat b ss l 17
- Technical specification 17
- Ewat b ss l 18
- Technical specification 18
- Ewat b ss l 19
- Technical specification 19
- Ewat b sr 20
- Technical specification 20
- Ewat b sr 21
- Technical specification 21
- Ewat b sr 22
- Technical specification 22
- Ewat b sr 23
- Technical specification 23
- Ewat b xs l 24
- Technical specification 24
- Ewat b xs l 25
- Technical specification 25
- Ewat b xs l 26
- Technical specification 26
- Ewat b xs l 27
- Technical specification 27
- Ewat b xr 28
- Technical specification 28
- Ewat b xr 29
- Technical specification 29
- Ewat b xr 30
- Technical specification 30
- Ewat b xr 31
- Technical specification 31
- Electrical specifications 32
- Ewat b ss l 32
- Electrical specifications 33
- Ewat b ss l 33
- Electrical specifications 34
- Ewat b sr 34
- Electrical specifications 35
- Ewat b sr 35
- Electrical specifications 36
- Ewat b xs l 36
- Electrical specifications 37
- Ewat b xs l 37
- Electrical specifications 38
- Ewat b xr 38
- Electrical specifications 39
- Ewat b xr 39
- Ewat b sl 40
- Ewat b ss 40
- Sound levels 40
- Ewat b sr 41
- Ewat b xs 41
- Sound levels 41
- Ewat b xl 42
- Ewat b xr 42
- Sound levels 42
- Amb t c 43
- Elwt c 43
- Ewat b s silver series 43
- Operating limits 43
- Units with multi v layout 43
- Units with single v layout 43
- Amb t c 44
- Elwt c 44
- Ewat b x gold series 44
- Multi v gold efficiency 44
- Options technical data 44
- Ref 3 ref 2 44
- Units with single v layout 44
- Air heat exchanger altitude correction factors 45
- Minimum glycol percentage for low air ambient temperature to prevent freezing of the hydraulic circuit 45
- Options technical data 45
- Water flow 45
- Water heat exchanger maximum maximum water δt 45
- Available fan static pressure correction factors 46
- Heat recovery 46
- Maximum cable dimension 46
- Options technical data 46
- Plant water conten 46
- Water quality 46
- Options technical data 47
- B c d e 48
- Ewat b s silver series single pump low lift 48
- Installations notes 48
- Multi v layout 48
- Single v layout 48
- Ewat b s silver series single pump high lift 49
- External pressure head kpa 49
- Installations notes 49
- Multi v layout 49
- Single v layout 49
- Water flow l s 49
- B c d e 50
- Ewat b s silver series twin pump low lift 50
- External static pressure kpa 50
- Installations notes 50
- Multi v layout 50
- Single v layout 50
- Water flow l s 50
- Ewat b x gold series single pump low lift 51
- External pressure head kpa 51
- External static pressure kpa 51
- H i j k 51
- Installations notes 51
- Multi v layout 51
- Single v layout 51
- Water flow l s 51
- Ewat b x gold series single pump high lift 52
- External pressure head kpa 52
- Installations notes 52
- Multi v layout 52
- Single v layout 52
- Water flow l s 52
- Ewat b x gold series twin pump low lift 53
- External static pressure kpa 53
- Installations notes 53
- Multi v layout 53
- Single v layout 53
- Water flow l s 53
- E i c b 54
- Ewat b x gold series twin pump high lift 54
- External pressure head kpa 54
- Installations notes 54
- Multi v layout 54
- Single v layout 54
- Water flow l s 54
- External pressure head kpa 55
- Installations notes 55
- Starting current with soft starter tank volume hydronic kit with tank 55
- Water filter pressure drops 55
- Installations notes 56
- Location 56
- Space requirements 56
- Warning 56
- Installations notes 57
- Multiple chillers installation closed area with wind prevalent direction 57
- Multiple chillers installation free field with wind prevalent direction 57
- Hydraulic schemes 58
- Installations notes 58
- Water filter 58
- Installations notes 59
- Technical specifications 59
- Installations notes 60
- Technical specifications 60
- Installations notes 61
- Technical specifications 61
Похожие устройства
- Daikin EWAT290B-SRB1 Руководство по эксплуатации
- Daikin EWAT290B-SRB1 Инструкция по эксплуатации
- Daikin EWAT290B-SRB1 Инструкция по монтажу
- Daikin EWAT310B-SRA2 Руководство по эксплуатации
- Daikin EWAT310B-SRA2 Технические данные
- Daikin EWAT310B-SRA2 Инструкция по эксплуатации
- Daikin EWAT310B-SRA2 Инструкция по монтажу
- Daikin EWAT310B-SRB2 Технические данные
- Daikin EWAT310B-SRB2 Руководство по эксплуатации
- Daikin EWAT310B-SRB2 Инструкция по эксплуатации
- Daikin EWAT310B-SRB2 Инструкция по монтажу
- Daikin EWAT330B-SRA2 Технические данные
- Daikin EWAT330B-SRA2 Руководство по эксплуатации
- Daikin EWAT330B-SRA2 Инструкция по эксплуатации
- Daikin EWAT330B-SRA2 Инструкция по монтажу
- Daikin EWAT330B-SRB2 Технические данные
- Daikin EWAT330B-SRB2 Руководство по эксплуатации
- Daikin EWAT330B-SRB2 Инструкция по эксплуатации
- Daikin EWAT330B-SRB2 Инструкция по монтажу
- Daikin EWAT340B-SRA1 Руководство по эксплуатации