Daikin EWAT290B-SRB1 [15/62] Installation options on request

Daikin EWAT260B-SRB2 [15/62] Installation options on request
15/62
OPTIONS
Note: opt.143 can be used only for units installed in a primary only plant to be controlled according to VPF
strategy. In case of multiple units installations in a primary only plant, to control the pump speed iCM is required.
Master/Slave function does not support primary only chilled water systems with variable flow operation.
Differential Pressure Transducers - shipped loose - (opt. code 144).
Daikin on site modem with antenna (opt. code 155)
Whenever LAN connection to the unit will not be available, connecting the unit to Daikin on Site will be possible
through a dedicated 3G M2M modem that can be ordered from Factory. When ordered, the modem will be
installed on the unit before leaving the Factory.
100 PA ESP fans (opt. code 160 Single V units only).
Special fans providing 100 Pa ESP. Unit power consumption is increasing.
200 PA ESP fans (opt. code 161 Multi V units only) option incompatibility 99-42-142a.
Special fans providing 100 Pa ESP. Unit power consumption is increasing.
Installation options On request
Rubber anti vibration mounts (opt. code 75) - option incompatibility 77.
Shipped loos, rubbe mounts are to be positioned under the base frame of the unit during installation. Ideal to
reduce the vibrations when the unit is floor mounted.
Spring anti vibration mounts (opt. code 77) - option incompatibility 75.
Shipped loos, spring mounts are to be positioned under the base frame of the unit during installation. Ideal for
dampening vibrations for installation on roofs and metallic structures.
External tank without cabinet 500 L (opt. code 83)
Inertial tank for chilled water storage - option incompatibility 84-87-88.
External tank without cabinet 1000 L (opt. code 84)
Inertial tank for chilled water storage - option incompatibility 83-87-88.
External tank with cabinet 500 L (opt. code 87)
Inertial tank for chilled water storage with cabinet - option incompatibility 83-84-88.
External tank with cabinet 1000 L (opt. code 88)
Inertial tank for chilled water storage with cabinet - option incompatibility 83-84-87.
Other options On request
Container kit (opt. code 71)
Specific solution designed to facilitate loading/unloading of the unit into the container and to reduce risk of
damage. - option incompatibility 112.
Transport kit (opt. code 112)
Specific solution that offers shocks’ absorption during unit transportation. - option incompatibility 71.