OPTIONS (TECHNICAL DATA)
44/62
EWAT~B-X (GOLD SERIES)
Ref 1 Operations below 4°C Evaporator Leaving Temperature require opt 08 (brine) and glycol
Ref 2 Units with Reduced Sound configuration might increase their sound level in this area
Ref 3 Certain unit sizes might work in part load in this area (Full load operation might need opt 142 - High Ambient Kit) Refer to
Chiller Selection Software for detailed information
Ref 4 In Multi-V units, operations below 10°C Ambient Temperature require Opt 99 (fan speed modulation) or Opt 42 (Speedtroll)
The above graph refers to the unit operating at full load. Unit may be able to operate outside the above envelope with compressors
unloading. Please contact factory for further details.
The above graphic represents a guideline about the operating limits of the range. Please refer to the latest Chiller Selection Software
(CSS) for real operating limits working conditions for each size.
-20
-10
0
10
20
30
40
50
-15 -10 -5 0 5 10 15 20 25
Amb T [
°C]
ELWT [°C]
Units with Single-V Layout
Ref 1
Ref 3
Ref 2
-20
-10
0
10
20
30
40
50
-15 -10 -5 0 5 10 15 20 25
Amb T [
°C]
ELWT [°C]
Multi V - Gold Efficiency
Ref 1
Ref 4
Ref 3
Ref 2