Daikin EUWYP10KAZW1 Сервис мануал онлайн [52/215] 527879

Daikin EUWYP10KAZW1 Сервис мануал онлайн [52/215] 527879
General Outline ESiE04-03
1–42 Part 1 – System Outline
3
11
4
5
Nominal conditions The nominal conditions are as follows:
Entering/leaving evaporator water temperature 12.5/7°C
Ambient air temperature 35°C
Power input is total input: Compressor + control circuit + fans + pump.
Operation range The nominal operation range covers:
A leaving evaporator water temperature from 5°C (-5°C/-20°C for ZH/ZL option) to 20°C (pull down
condition to 25°C).
A leaving condensor water temperature from 35°C to 50°C.

Содержание