Capacity Tables ED43-441
26 Packaged Air Conditioners UATY-K Series
7. Capacity Tables
7.1 Cooling Capacity [50Hz]
UATY06KY1
UATY08KY1
(m³/min.)
(˚CWB)
(˚CDB)
(kW)
(kW)
(kW)
Symbols:
AFR
BF
EWB
EDB
TC
SHC
PI
: Air flow rate
: Bypass factor
: Entering wet bulb temp.
: Entering dry bulb temp.
: Total cooling capacity
: Sensible heat capacity
: Power input
(Comp.+outdoor fan motor).
Notes:
1. Direct interpolation is permissible.
Do not extrapolate beyond the Operation Limits.
2. shows nominal capacities.
3. SHC is based on each EWB and EDB.
SHC*=SHC correction for other dry bulb. (DB*)
=0.02×AFR×(1-BF)×(DB*-EDB)
Add SHC* to SHC.
4. Above cooling capacities do not include indoor fan motor heat.
3D014894A
AFR(BF)
47
(0.15)
52
(0.16)
62
(0.18)
EWB(˚C)
14.0
16.0
18.0
19.0
19.5
22.0
24.0
14.0
16.0
18.0
19.0
19.5
22.0
24.0
14.0
16.0
18.0
19.0
19.5
22.0
24.0
EDB(˚C)
20.0
22.0
25.0
27.0
27.0
30.0
32.0
20.0
22.0
25.0
27.0
27.0
30.0
32.0
20.0
22.0
25.0
27.0
27.0
30.0
32.0
TC
15.9
16.9
18.0
18.5
18.8
20.3
21.6
16.2
17.2
18.3
18.9
19.2
20.7
21.9
16.6
17.8
18.8
19.4
19.7
21.3
22.6
SHC
12.0
12.1
12.8
13.4
13.1
13.4
13.3
12.5
12.5
13.3
14.0
13.6
14.0
13.9
13.3
13.4
14.2
15.0
14.6
15.0
14.9
PI
4.6
4.7
4.8
4.8
4.8
5.0
5.1
4.6
4.7
4.8
4.8
4.9
5.0
5.2
4.6
4.7
4.8
4.9
4.9
5.1
5.2
TC
15.2
16.3
17.3
17.8
18.1
19.6
20.8
15.5
16.5
17.6
18.2
18.4
19.9
21.1
16.0
17.0
18.1
18.7
19.0
20.4
21.7
SHC
11.7
11.7
12.4
13.1
12.7
13.0
13.0
12.1
12.2
12.9
13.6
13.3
13.6
13.5
12.9
13.0
13.8
14.6
14.2
14.6
14.6
PI
5.0
5.1
5.2
5.2
5.3
5.4
5.6
5.0
5.1
5.2
5.3
5.3
5.5
5.6
5.0
5.2
5.3
5.3
5.4
5.5
5.7
TC
14.6
15.6
16.6
17.1
17.4
18.8
19.9
14.8
15.8
16.9
17.4
17.7
19.1
20.3
15.3
16.3
17.3
17.9
18.1
19.6
20.8
SHC
11.3
11.3
12.0
12.7
12.4
12.7
12.6
11.7
11.8
12.5
13.2
12.9
13.2
13.2
12.5
12.6
13.4
14.2
13.8
14.2
14.2
PI
5.4
5.6
5.7
5.8
5.8
5.9
6.1
5.5
5.6
5.7
5.8
5.8
6.0
6.1
5.5
5.6
5.8
5.8
5.9
6.0
6.2
TC
13.9
14.8
15.8
16.3
16.6
17.9
19.1
14.1
18.6
16.1
16.6
16.9
18.2
19.4
14.5
15.5
16.5
17.0
17.3
18.7
19.8
SHC
10.9
10.9
11.6
12.3
12.0
12.3
12.2
11.3
14.0
12.1
12.8
12.5
12.8
12.8
12.0
12.1
13.0
13.8
13.4
13.8
13.8
PI
6.0
6.1
6.2
6.3
6.3
6.5
6.6
6.0
6.1
6.2
6.3
6.3
6.5
6.7
6.0
6.2
6.3
6.4
6.4
6.6
6.7
TC
13.2
14.1
15.0
15.5
15.8
17.1
18.1
13.3
14.3
15.3
15.7
16.0
17.3
18.4
13.7
14.7
15.6
16.1
16.4
17.7
18.8
SHC
10.5
10.5
11.2
11.9
11.6
11.9
11.8
10.8
10.9
11.7
12.4
12.1
12.4
12.4
11.6
11.7
12.5
13.3
12.9
13.4
13.3
PI
6.5
6.7
6.8
6.9
6.9
7.1
7.2
6.6
6.7
6.8
6.9
6.9
7.1
7.3
6.6
6.7
6.9
7.0
7.0
7.2
7.3
TC
12.4
13.3
14.1
14.6
14.9
16.1
12.6
13.5
14.4
14.8
15.1
16.4
12.9
13.8
14.7
15.2
15.4
16.7
SHC
10.0
10.1
10.8
11.5
11.1
11.5
10.4
10.5
11.2
12.0
11.6
12.0
11.1
11.2
12.0
12.8
12.5
12.9
PI
7.2
7.3
7.4
7.5
7.5
7.7
7.2
7.3
7.5
7.5
7.6
7.8
7.2
7.4
7.5
7.6
7.6
7.8
TC
12.4
13.3
14.1
14.6
14.9
16.1
12.6
13.5
14.4
14.8
15.1
16.4
12.9
13.8
14.7
15.2
15.4
16.7
SHC
10.0
10.1
10.8
11.5
11.1
11.5
10.4
10.5
11.2
12.0
11.6
12.0
11.1
11.2
12.0
12.8
12.5
12.9
PI
7.2
7.3
7.4
7.5
7.5
7.7
7.2
7.3
7.5
7.5
7.6
7.8
7.2
7.4
7.5
7.6
7.6
7.8
25 30 35 40 45 50 52
Indoor air
Outdoor temp. (˚CDB)
(m³/min.)
(˚CWB)
(˚CDB)
(kW)
(kW)
(kW)
Symbols:
AFR
BF
EWB
EDB
TC
SHC
PI
: Air flow rate
: Bypass factor
: Entering wet bulb temp.
: Entering dry bulb temp.
: Total cooling capacity
: Sensible heat capacity
: Power input
(Comp.+outdoor fan motor).
3D014898A
Notes:
1. Direct interpolation is permissible.
Do not extrapolate beyond the Operation Limits.
2. shows nominal capacities.
3. SHC is based on each EWB and EDB.
SHC*=SHC correction for other dry bulb. (DB*)
=0.02×AFR×(1-BF)×(DB*-EDB)
Add SHC* to SHC.
4. Above cooling capacities do not include indoor fan motor heat.