Daikin FXCQ63AVEB [10/30] Do not peel off the film adhered on the side if peeled off the operating sound may become larger

Daikin FXCQ125AVEB [10/30] Do not peel off the film adhered on the side if peeled off the operating sound may become larger
9 English
[In case of existing ceiling]
Cut off the guides from the installation pattern paper (5) and place the guide to the indoor unit bottom.
Adjust the unit height from the floor level so that the ceiling lower surface and the notch lower part will
match together. (Refer to Fig. 5)
< Installation work after the ceiling work is finished >
(3) Adjust so that the unit will be properly positioned.
( Refer to “4. PREPARATION BEFORE INSTALLATION – (1)” )
(4) Check the level of the unit. (Refer to Fig. 6)
(5) Remove the washer clamp (7) used for preventing the washer for hanger (3) from dropping and tighten the
upper side nut.
(6) Remove the installation pattern paper (5).
[To attach the installation pattern paper]
Do not peel off the film adhered on the side.
(If peeled off, the operating sound may become
larger.)
Installation pattern paper (5)
(accessory)
Screw (6)
(accessory)
Fig. 4
[To adjust the unit height from the floor level]
Indoor unit
Guide
Ceiling board
Notch
Notch lower part
Installation pattern paper (5)
(accessory)
Guide
(at 4 corners)
Fig. 5
Ceiling lower surface
[To ensure level]
Level
Pour water into the tube and
have the indoor unit match the
height of water surface of the
both sides.
Polyvinyl chloride tube
Fig. 6
01_EN_3P249378-7M.fm Page 9 Wednesday, September 12, 2012 1:05 PM