Daikin FXAQ40MAVET [160/264] H9 outdoor unit malfunction of thermistor r1t for outdoor air

Daikin FXCQ63M8V3B [160/264] H9 outdoor unit malfunction of thermistor r1t for outdoor air
SiBE34-703 Troubleshooting by Indication on the Remote Controller
Troubleshooting 149
3.22 H9 Outdoor Unit: Malfunction of Thermistor (R1T) for
Outdoor Air
Remote
Controller
Display
H9
Applicable
Models
RXYSQ4~6P
Method of
Malfunction
Detection
Malfunction is detected from the temperature detected by the outdoor air thermistor.
Malfunction
Decision
Conditions
When the outside air temperature thermistor has short circuit or open circuit.
Supposed
Causes
Defect of thermistor (R1T) for outdoor air
Defect of outdoor unit PC board (A1P)
Troubleshooting
Refer to “Thermistor Resistance / Temperature Characteristics” table on P223.
(V3070)
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Resistance
is normal when
measured after
disconnecting the thermistor
(R1T) from the outdoor
unit PC board.
(3.5k to
360k)
Connector is
connected to X11A of
outdoor PC board
(A1P).
Replace outdoor unit PC board
(A1P).
Connect the connector and turn on
again.
NO
NO
Replace the thermistor (R1T).
YES
YES