Special Control SiBE34-703
50 Function
3.5 Restart Standby
Restart is stood by force to prevent frequent power-on/off and to equalize pressure in the
refrigerant system.
Actuator Operation Remarks
Compressor OFF
Outdoor unit fan
Ta>30°C: STEP4
Ta30°C: OFF
Four way valve Keep former condition.
Main electronic expansion valve (EV1) 0 pls
Subcooling electronic expansion valve
(EV3)
0 pls
Hot gas bypass valve (SVP) OFF
Ending conditions 2 min.