Si34-803 Troubleshooting by Indication on the Remote Controller
Troubleshooting 291
3.22
E7
Outdoor Unit: Malfunction of Outdoor Unit Fan
Motor
Remote
Controller
Display
E7
Applicable
Models
RXYQ5P(A)~54P(A)
Method of
Malfunction
Detection
Malfunction of fan motor system is detected according to the fan speed detected by hall IC
when the fan motor runs.
Malfunction
Decision
Conditions
When the fan runs with speed less than a specified one for 6 seconds or more when the fan
motor running conditions are met
When connector detecting fan speed is disconnected
When malfunction is generated 4 times, the system shuts down.
Supposed
Causes
Malfunction of fan motor
The harness connector between fan motor and PC board is left in disconnected, or faulty
connector
Fan does not run due to foreign matters tangled
Clearing condition: Operate for 5 minutes (normal)