Troubleshooting by Indication on the Remote Controller Si34-803
304 Troubleshooting
3.32
J7
Outdoor Unit: Malfunction of Liquid Pipe Thermistor
(R6T)
Remote
Controller
Display
J7
Applicable
Models
RXYQ5P(A)~54P(A)
Method of
Malfunction
Detection
Malfunction is detected according to the temperature detected by liquid pipe thermistor.
Malfunction
Decision
Conditions
When the liquid pipe thermistor is short circuited or open.
Supposed
Causes
Faulty liquid pipe thermistor (R6T)
Faulty outdoor unit PC board
Defect of thermistor connection
Troubleshooting
Refer to “Thermistor Resistance / Temperature Characteristics” table on P.427.
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Is the
resistance
measured after
removing the thermistor
(R6T) from outdoor unit PC
board normal?
(1.8k to
800k)
Replace outdoor unit PC board
(A1P).
Connect the connector and
operate unit again.
NO
NO
Replace thermistor (R6T).
YES
YES
Is
the connector
for liquid pipe
thermistor connected to
X30A on outdoor
unit PC board
(A1P)?