Daikin FXDQ40A3VEB [13/18] Wiring example
![Daikin FXDQ40A3VEB [13/18] Wiring example](/views2/1704002/page13/bgd.png)
English 11
•
Remote controller and transmission wiring
Pull the wires into the unit through the wiring through hole
and connect to the terminal block (6P).
Be sure to put the part of the sheathed vinyl into the control
box.
Precautions when laying power supply wiring
•
Wiring of different thicknesses cannot be connected to the
power supply wiring terminal block. (Slack in the power sup-
ply wiring may cause abnormal heat.)
•
Use sleeve-insulated round crimp-style terminals for connec-
tions to the power supply wiring terminal block. When none
are available, connect wires of the same diameter to both
sides, as shown in the figure.
Follow the instructions are below if the wiring may get very
hot due to slack in the power supply wiring.
•
For wiring, use the designated power supply wiring and con-
nect firmly, then secure to prevent outside pressure being
exerted on the terminal board.
•
Use the correct screwdriver for tightening the terminal
screws. If the blade of screwdriver is too small, the head of
the screw might be damaged, and the screw will not be prop-
erly tightened.
•
If the terminal screws are tightened too hard, screws might
be damaged.
•
Refer to the table below for the tightening torque of the termi-
nal screws.
[ WIRING EXAMPLE ]
No. 1 system When using 1 remote controller for
1 indoor unit
No. 2 system For group control or use with 2 remote
controllers
Terminal block Tightening torque (N·m)
Remote controller / transmission wiring
terminal block (6P)
0.79 – 0.97
Power supply wiring terminal block (3P) 1.18 – 1.44
Insulation sleeve
Round crimp-style terminal
Electric wire
Do not connect
wires of different
gauges.
Do not connect
wires of the same
gauge to one side.
Connect wires of
the same gauge to
both sides.
FT
1
L
1
1
1
PP
2
P
N
1
2
P
T
F
2
F
P
F
1
2
2
2
P
1
N
2
P
2
F
IN/D
1
OUT/D
1
P
F
2
F
1
P
L
F
1 2
T
2
T
1
PP
21
F
2
N
F
L
12
TT
P
LN LN LN
(option) (option) (option)
Fig. 19
Remote controllerRemote controllerRemote controller
Outdoor unit
Power supply
single phase
50Hz 220-240V
or single phase
60Hz 220V
Power supply
single phase
50Hz 220-240V
or single phase
60Hz 220V
Power supply
single phase
50Hz 220-240V
or single phase
60Hz 220V
Most
downstream
indoor unit
Indoor unit BIndoor unit A
LN
1
P
2
P
1
P
2
P
1
P
2
P
1
PP
21
F
2
N
F
L
NL
12
FF
1 2
FF
1 2
TT
1
PP
21
F
2
F
12
TT
NL
1
PP
21
F
2
F
12
TT
IN/D
OUT/D
Power supply
single phase
50Hz 220-240V
or single phase
60Hz 220V
(option)
(option)
Remote controller
Remote controller
Remote controller
Fig. 20
Case of group control
For use with 2
remote controllers
Most
downstream
indoor unit
Indoor unit B
Indoor
unit A
Note) There is not need to set the indoor unit
address when using group control.
(It is automatically set when the power
is turned on.)
Outdoor unit
4PEN325876-1F.book Page 11 Thursday, April 20, 2017 8:20 AM
Содержание
- Installation manual 1
- System inverter air conditioners 1
- Daikin industries czech republic s r o 2
- En60335 2 4 2
- Fxdq15a3veb fxdq20a3veb fxdq25a3veb fxdq32a3veb fxdq40a3veb fxdq50a3veb fxdq63a3veb 2
- Machinery 2006 42 ec electromagnetic compatibility 2014 30 eu 2
- P481419 1 2
- P481419 1_fxdq15 63a3veb fm page 1 monday april 24 2017 10 01 am 2
- Tetsuya baba managing director pilsen 2nd of may 2017 2
- Contents 3
- Safety precautions 3
- 1 precautions 4
- 2 accessories 4
- 3 optional accessories 4
- Before installation 4
- For the following items take special care during construction and check after installation is finished 4
- Selecting installation site 5
- Preparations before installation 6
- In case of back side in case of bottom side 7
- Indoor unit installation 7
- Refrigerant piping work 7
- Drain piping work 9
- Installing the duct 10
- 1 general instructions 11
- 2 specifications for field supplied fuses and wire 11
- 3 electrical characteristics 11
- A circuit breaker capable of shutting down power supply to the entire system must be installed 11
- All field supplied parts and materials electric works must conform to local codes 11
- All wiring must be performed by an authorized electrician 11
- Be sure to ground the air conditioner 11
- Do not the earth wire should come in contact with gas pipes water pipes lightning rods or telephone earth wires 11
- Do not turn on the power supply circuit breaker or earth leak age breaker until all other work is done 11
- Electric wiring work 11
- English 9 11
- For details on hooking up the remote controller refer to the remote controller installation manual 11
- Gas pipes gas leaks can cause explosions and fire 11
- Length of the transmission wiring and remote controller wiring 11
- Mca minimum circuit amps a mfa max fuse amps a kw fan motor output kw fla full load amps a 11
- Power related 11
- Refer to the installation manual attached to the outdoor unit for the size of power supply wiring connected to the outdoor unit the capacity of the circuit breaker and switch and wiring instructions 11
- See also the wiring diagram plate attached to the control box lid when laying electrical wiring 11
- Shows only in case of protected pipes use h07rn f in case of no protection 2 insulated thickness 1mm or more 3 if the wiring is in a place where people it can be easily touched by people install an earth leakage breaker to pre vent electric shock 4 when using an earth leakage breaker make sure to select one useful also to protection against overcurrent and short circuit when using an earth leakage breaker only for earth device make sure to use a wiring interrupter together 11
- Shut off the power before doing any work 11
- Telephone earth wire and lightning rods the ground potential when struck by lightning gets extremely high 11
- The length of the transmission wiring and remote controller wiring are as follows 11
- This system consists of multiple indoor units mark each indoor unit as unit a unit b and be sure the terminal board wiring to the outdoor unit and bs unit are properly matched if wiring and piping between the outdoor unit and an indoor unit are mismatched the system may cause a malfunction 11
- To avoid short circuiting the power supply wire be sure to use insulated terminals 11
- Use copper wire only 11
- Water pipes they cannot be grounded if hard vinyl pipes are used 11
- 1 how to connect wirings 12
- Wiring example 12
- Precautions when laying power supply wiring 13
- Wiring example 13
- 2 control by 2 remote controllers con trolling 1 indoor unit by 2 remote controllers 14
- 3 remote control forced off and on off operation 14
- 4 centralized control 14
- Field setting and test run 14
- 1 setting the static pressure selection 15
- 2 remote control setting 15
- 3 setting the filter sign display interval 15
- 4 settings for separately sold accessories 15
- Field setting and test run 15
- Field settings may have to be performed using the remote controller depending on the type of installation 15
- English 16
- Unified wiring diagram legend 16
- Wiring diagram 16
Похожие устройства
- Daikin FXDQ40A3VEB Технические данные
- Daikin FXDQ50A3VEB Инструкция по эксплуатации
- Daikin FXDQ50A3VEB Инструкция по монтажу
- Daikin FXDQ50A3VEB Технические данные
- Daikin FXDQ63A3VEB Инструкция по эксплуатации
- Daikin FXDQ63A3VEB Инструкция по монтажу
- Daikin FXDQ63A3VEB Технические данные
- MEAN WELL OWA-60E-12 Инструкция по эксплуатации
- MEAN WELL OWA-60E-12 Инструкция язык EN
- MEAN WELL OWA-60E-12 Datasheet
- MEAN WELL OWA-60E-12 Документация
- MEAN WELL OWA-60E-15 Инструкция по эксплуатации
- MEAN WELL OWA-60E-15 Инструкция язык EN
- MEAN WELL OWA-60E-15 Datasheet
- MEAN WELL OWA-60E-15 Документация
- MEAN WELL OWA-60E-20 Инструкция по эксплуатации
- MEAN WELL OWA-60E-20 Инструкция язык EN
- MEAN WELL OWA-60E-20 Datasheet
- MEAN WELL OWA-60E-20 Документация
- MEAN WELL OWA-60E-24 Инструкция по эксплуатации