Daikin FXDQ40A3VEB [7/18] In case of back side in case of bottom side
![Daikin FXDQ40A3VEB [7/18] In case of back side in case of bottom side](/views2/1704002/page7/bg7.png)
English 5
5. INDOOR UNIT INSTALLATION
As for the parts to be used for installation work, be sure to
use the provided accessories and specified parts desig-
nated by our company.
(1)
Install the indoor unit temporarily.
•
Attach the hanger bracket to the suspension bolt. Be sure
to fix it securely by using a nut and washer from the upper
and lower sides of the hanger bracket.
(Refer to Fig. 5)
[ PRECAUTION ]
Since the unit uses a plastic drain pan, prevent welding
spatter and other foreign substances from the air outlet
during installation.
(2)
Adjust the height of the unit.
(3)
Check the unit is horizontally level.
CAUTION
•
Make sure the unit is installed level using a level or a
plastic tube filled with water. In using a plastic tube
instead of a level, adjust the top surface of the unit to the
surface of the water at both ends of the plastic tube and
adjust the unit horizontally. (One thing to watch out for in
particular is if the unit is installed so that the slope is not
in the direction of the drain piping, this might cause leak-
ing.)
(4)
Tighten the upper nut.
6. REFRIGERANT PIPING WORK
For refrigerant piping of outdoor units, see the installation
manual attached to the outdoor unit.
Execute heat insulation work completely on both sides of
the gas piping and the liquid piping. Otherwise, a water
leakage can result sometimes.
Use insulation that can withstand temperatures of at least
120°C. Reinforce the insulation on the refrigerant piping
according to the installation environment. If the tempera-
ture above the ceiling might reach 30°C or the humidity
RH80%. Condensation may form on the surface of the insu-
lation.
CAUTION
Follow the points at below.
•
Use a pipe cutter and flare suitable for the type of refrigerant.
•
Apply ester oil or ether oil to the flare section when using a
flare connection.
•
Only use the flare nuts included with the unit. Using different
flare nuts may cause the refrigerant to leak.
•
To prevent dust, moisture or other foreign matter from infil-
trating the piping, either pinch the end or cover it with tape.
•
Do not allow anything other than the designated refrigerant
to get mixed into the refrigerant circuit, such as air, etc. If any
refrigerant gas leaks while working on the unit, ventilate the
room thoroughly right away.
(1)
Connect the piping.
•
The outdoor unit is charged with refrigerant.
•
Be sure to use both a spanner and torque wrench together,
as shown in the drawing, when connecting or disconnecting
pipes to/from the unit. (Refer to Fig. 6)
•
Refer to the Table 1 for the dimensions of flare nut spaces.
•
Apply ester oil or ether oil to flare section (both inside and
out) when using flare nut connections and then turn 3 or 4
times by hand. (Refer to Fig. 7)
(3)
Attach the filter to the
main unit while pushing
down on the bends.
Main unit
Force
Force
Filter
In case of back side
In case of bottom side
(accessory)
(accessory)
Washer fixing plate (11)
Insert below washer
Fig. 5
Tighten
(double nut)
Hanger
bracket
Washer for
hanging bracket (8)
[ How to secure washers ][ Securing the hanger bracket ]
Part to be procured
in the field
Level
Vinyl tube
Fig. 7Fig. 6
Flare nut
Piping union
Ester oil or ether oil
Spanner
Torque wrench
4PEN325876-1F.book Page 5 Thursday, April 20, 2017 8:20 AM
Содержание
- Installation manual 1
- System inverter air conditioners 1
- Daikin industries czech republic s r o 2
- En60335 2 4 2
- Fxdq15a3veb fxdq20a3veb fxdq25a3veb fxdq32a3veb fxdq40a3veb fxdq50a3veb fxdq63a3veb 2
- Machinery 2006 42 ec electromagnetic compatibility 2014 30 eu 2
- P481419 1 2
- P481419 1_fxdq15 63a3veb fm page 1 monday april 24 2017 10 01 am 2
- Tetsuya baba managing director pilsen 2nd of may 2017 2
- Contents 3
- Safety precautions 3
- 1 precautions 4
- 2 accessories 4
- 3 optional accessories 4
- Before installation 4
- For the following items take special care during construction and check after installation is finished 4
- Selecting installation site 5
- Preparations before installation 6
- In case of back side in case of bottom side 7
- Indoor unit installation 7
- Refrigerant piping work 7
- Drain piping work 9
- Installing the duct 10
- 1 general instructions 11
- 2 specifications for field supplied fuses and wire 11
- 3 electrical characteristics 11
- A circuit breaker capable of shutting down power supply to the entire system must be installed 11
- All field supplied parts and materials electric works must conform to local codes 11
- All wiring must be performed by an authorized electrician 11
- Be sure to ground the air conditioner 11
- Do not the earth wire should come in contact with gas pipes water pipes lightning rods or telephone earth wires 11
- Do not turn on the power supply circuit breaker or earth leak age breaker until all other work is done 11
- Electric wiring work 11
- English 9 11
- For details on hooking up the remote controller refer to the remote controller installation manual 11
- Gas pipes gas leaks can cause explosions and fire 11
- Length of the transmission wiring and remote controller wiring 11
- Mca minimum circuit amps a mfa max fuse amps a kw fan motor output kw fla full load amps a 11
- Power related 11
- Refer to the installation manual attached to the outdoor unit for the size of power supply wiring connected to the outdoor unit the capacity of the circuit breaker and switch and wiring instructions 11
- See also the wiring diagram plate attached to the control box lid when laying electrical wiring 11
- Shows only in case of protected pipes use h07rn f in case of no protection 2 insulated thickness 1mm or more 3 if the wiring is in a place where people it can be easily touched by people install an earth leakage breaker to pre vent electric shock 4 when using an earth leakage breaker make sure to select one useful also to protection against overcurrent and short circuit when using an earth leakage breaker only for earth device make sure to use a wiring interrupter together 11
- Shut off the power before doing any work 11
- Telephone earth wire and lightning rods the ground potential when struck by lightning gets extremely high 11
- The length of the transmission wiring and remote controller wiring are as follows 11
- This system consists of multiple indoor units mark each indoor unit as unit a unit b and be sure the terminal board wiring to the outdoor unit and bs unit are properly matched if wiring and piping between the outdoor unit and an indoor unit are mismatched the system may cause a malfunction 11
- To avoid short circuiting the power supply wire be sure to use insulated terminals 11
- Use copper wire only 11
- Water pipes they cannot be grounded if hard vinyl pipes are used 11
- 1 how to connect wirings 12
- Wiring example 12
- Precautions when laying power supply wiring 13
- Wiring example 13
- 2 control by 2 remote controllers con trolling 1 indoor unit by 2 remote controllers 14
- 3 remote control forced off and on off operation 14
- 4 centralized control 14
- Field setting and test run 14
- 1 setting the static pressure selection 15
- 2 remote control setting 15
- 3 setting the filter sign display interval 15
- 4 settings for separately sold accessories 15
- Field setting and test run 15
- Field settings may have to be performed using the remote controller depending on the type of installation 15
- English 16
- Unified wiring diagram legend 16
- Wiring diagram 16
Похожие устройства
- Daikin FXDQ40A3VEB Технические данные
- Daikin FXDQ50A3VEB Инструкция по эксплуатации
- Daikin FXDQ50A3VEB Инструкция по монтажу
- Daikin FXDQ50A3VEB Технические данные
- Daikin FXDQ63A3VEB Инструкция по эксплуатации
- Daikin FXDQ63A3VEB Инструкция по монтажу
- Daikin FXDQ63A3VEB Технические данные
- MEAN WELL OWA-60E-12 Инструкция по эксплуатации
- MEAN WELL OWA-60E-12 Инструкция язык EN
- MEAN WELL OWA-60E-12 Datasheet
- MEAN WELL OWA-60E-12 Документация
- MEAN WELL OWA-60E-15 Инструкция по эксплуатации
- MEAN WELL OWA-60E-15 Инструкция язык EN
- MEAN WELL OWA-60E-15 Datasheet
- MEAN WELL OWA-60E-15 Документация
- MEAN WELL OWA-60E-20 Инструкция по эксплуатации
- MEAN WELL OWA-60E-20 Инструкция язык EN
- MEAN WELL OWA-60E-20 Datasheet
- MEAN WELL OWA-60E-20 Документация
- MEAN WELL OWA-60E-24 Инструкция по эксплуатации