8 English
1.
Remove the control box lid. Connect the remote controller
and power supply (single-phase, 50 Hz 220-240 V or sin-
gle-phase, 60Hz 220V) respectively to the terminal block
and securely connect the earth also (as shown in the figure
below).
CAUTION
Securely clamp the cables with the clamps (9)(10) offered
as accessories as shown in Fig. 17 so that tension will not
be applied on the cable connection areas.
2.
Confirm that the control box lid is closed before turning on
the power.
3.
Remove the inspection lid.
4.
Gradually pour approximately 1L of water from the inspec-
tion window into the drain pan to check drainage.
CAUTION
Be sure to prevent an external force from being exerted on
the float switch.
(This may cause breakage.)
5.
Attach the inspection lid.
6.
Perform the following operation using the remote controller,
and check drainage.
•
Select the inspection/test operation button “ ” using
the remote controller. The unit will engage the test oper-
ation. Press the operation selector button “ ”, and
select FAN OPERATION “ ”.
•
Press the ON/OFF button “ ”. (The indoor fan and drain
pump will operate.)
CAUTION
The fan will turn also at the same time. Take due care.
Do not touch the drain pump to prevent electric shock.
7.
Make sure to use the remote controller in finishing the oper-
ation.
8. INSTALLING THE DUCT
Connect the duct supplied in the field.
Air inlet side
•
Attach the duct and intake-side flange (field supply).
•
Connect the flange to the main unit with accessory screws
(7).
•
Wrap the intake-side flange and duct connection area with
aluminum tape or something similar to prevent air escaping.
CAUTION
When attaching a duct to the intake side, be sure to attach an air
filter inside the air passage on the intake side. (Use an air filter
whose dust collecting efficiency is at least 50% in a gravimetric
technique.)
The included filter is not used when the intake duct is attached.
Air outlet side
•
Connect the duct according to the air inside of the outlet-side
flange.
•
Wrap the outlet-side flange and the duct connection area
with aluminum tape or something similar to prevent air
escaping.
CAUTION
•
Be sure to insulate the duct to prevent condensation from
forming. (Material: glass wool or polyethylene foam, 25 mm
thick)
•
Use electric insulation between the duct and the wall when
using metal ducts to pass metal laths of the net or fence
shape or metal plating into wooden buildings.
•
Be sure to explain about the way of maintaining and cleaning
local procurements (air filter, grille (both air outlet and suction
grille), etc.) to your customer.
TEST
TRANSMISSION
WIRING
REMOTE
CNTRL
T1F1
FORCED
OFF
P2 F2P1 T2
NL
L N
Power supply:
Single phase,
50 Hz, 220 V–
240V
Single phase,
60Hz, 220 V
Power terminal
connection
method
Remote controller
terminal connection
method
Terminal block
Terminal block
Indoor PCboard
(ASSY)
(with rubber cap)
Drain outlet
Service drain hole
Bucket
Refrigerant pipes
Inspection lid
Portable pump
Inspection window
Class 15 · 20 · 25 · 32 40 · 50 63
Number of
positions
16 22 26
Air outlet side
Air inlet side
Insulation
material
Main unit
Aluminum tape
Aluminum tape
Flange
Flange
(Field supply)
(Field supply)
(Field supply)
(Field supply)
(accessory)
Connection screw (7)
4PEN325876-1F.book Page 8 Thursday, April 20, 2017 8:20 AM
Содержание
- Installation manual 1
- System inverter air conditioners 1
- Daikin industries czech republic s r o 2
- En60335 2 4 2
- Fxdq15a3veb fxdq20a3veb fxdq25a3veb fxdq32a3veb fxdq40a3veb fxdq50a3veb fxdq63a3veb 2
- Machinery 2006 42 ec electromagnetic compatibility 2014 30 eu 2
- P481419 1 2
- P481419 1_fxdq15 63a3veb fm page 1 monday april 24 2017 10 01 am 2
- Tetsuya baba managing director pilsen 2nd of may 2017 2
- Contents 3
- Safety precautions 3
- 1 precautions 4
- 2 accessories 4
- 3 optional accessories 4
- Before installation 4
- For the following items take special care during construction and check after installation is finished 4
- Selecting installation site 5
- Preparations before installation 6
- In case of back side in case of bottom side 7
- Indoor unit installation 7
- Refrigerant piping work 7
- Drain piping work 9
- Installing the duct 10
- 1 general instructions 11
- 2 specifications for field supplied fuses and wire 11
- 3 electrical characteristics 11
- A circuit breaker capable of shutting down power supply to the entire system must be installed 11
- All field supplied parts and materials electric works must conform to local codes 11
- All wiring must be performed by an authorized electrician 11
- Be sure to ground the air conditioner 11
- Do not the earth wire should come in contact with gas pipes water pipes lightning rods or telephone earth wires 11
- Do not turn on the power supply circuit breaker or earth leak age breaker until all other work is done 11
- Electric wiring work 11
- English 9 11
- For details on hooking up the remote controller refer to the remote controller installation manual 11
- Gas pipes gas leaks can cause explosions and fire 11
- Length of the transmission wiring and remote controller wiring 11
- Mca minimum circuit amps a mfa max fuse amps a kw fan motor output kw fla full load amps a 11
- Power related 11
- Refer to the installation manual attached to the outdoor unit for the size of power supply wiring connected to the outdoor unit the capacity of the circuit breaker and switch and wiring instructions 11
- See also the wiring diagram plate attached to the control box lid when laying electrical wiring 11
- Shows only in case of protected pipes use h07rn f in case of no protection 2 insulated thickness 1mm or more 3 if the wiring is in a place where people it can be easily touched by people install an earth leakage breaker to pre vent electric shock 4 when using an earth leakage breaker make sure to select one useful also to protection against overcurrent and short circuit when using an earth leakage breaker only for earth device make sure to use a wiring interrupter together 11
- Shut off the power before doing any work 11
- Telephone earth wire and lightning rods the ground potential when struck by lightning gets extremely high 11
- The length of the transmission wiring and remote controller wiring are as follows 11
- This system consists of multiple indoor units mark each indoor unit as unit a unit b and be sure the terminal board wiring to the outdoor unit and bs unit are properly matched if wiring and piping between the outdoor unit and an indoor unit are mismatched the system may cause a malfunction 11
- To avoid short circuiting the power supply wire be sure to use insulated terminals 11
- Use copper wire only 11
- Water pipes they cannot be grounded if hard vinyl pipes are used 11
- 1 how to connect wirings 12
- Wiring example 12
- Precautions when laying power supply wiring 13
- Wiring example 13
- 2 control by 2 remote controllers con trolling 1 indoor unit by 2 remote controllers 14
- 3 remote control forced off and on off operation 14
- 4 centralized control 14
- Field setting and test run 14
- 1 setting the static pressure selection 15
- 2 remote control setting 15
- 3 setting the filter sign display interval 15
- 4 settings for separately sold accessories 15
- Field setting and test run 15
- Field settings may have to be performed using the remote controller depending on the type of installation 15
- English 16
- Unified wiring diagram legend 16
- Wiring diagram 16
Похожие устройства
- Daikin FXDQ63A3VEB Технические данные
- MEAN WELL OWA-60E-12 Инструкция по эксплуатации
- MEAN WELL OWA-60E-12 Инструкция язык EN
- MEAN WELL OWA-60E-12 Datasheet
- MEAN WELL OWA-60E-12 Документация
- MEAN WELL OWA-60E-15 Инструкция по эксплуатации
- MEAN WELL OWA-60E-15 Инструкция язык EN
- MEAN WELL OWA-60E-15 Datasheet
- MEAN WELL OWA-60E-15 Документация
- MEAN WELL OWA-60E-20 Инструкция по эксплуатации
- MEAN WELL OWA-60E-20 Инструкция язык EN
- MEAN WELL OWA-60E-20 Datasheet
- MEAN WELL OWA-60E-20 Документация
- MEAN WELL OWA-60E-24 Инструкция по эксплуатации
- MEAN WELL OWA-60E-24 Инструкция язык EN
- MEAN WELL OWA-60E-24 Datasheet
- MEAN WELL OWA-60E-24 Документация
- MEAN WELL OWA-60E-30 Инструкция по эксплуатации
- MEAN WELL OWA-60E-30 Инструкция язык EN
- MEAN WELL OWA-60E-30 Datasheet