Daikin FXSQ20MVE [295/458] Remote controller display

Daikin FXSQ20MVE [295/458] Remote controller display
Troubleshooting by Indication on the Remote Controller Si34-803
284 Troubleshooting
3.18
E3
Outdoor Unit: Actuation of High Pressure Switch
Remote
Controller
Display
E3
Applicable
Models
RXYQ5P(A)~54P(A)
Method of
Malfunction
Detection
Abnormality is detected when the contact of the high pressure protection switch opens.
Malfunction
Decision
Conditions
Error is generated when the HPS activation count reaches the number specific to the operation
mode.
(Reference) Operating pressure of high pressure switch
Operating pressure:4.0MPa
Reset pressure: 2.85MPa
Supposed
Causes
Actuation of outdoor unit high pressure switch
Defect of High pressure switch
Defect of outdoor unit PC board
Instantaneous power failure
Faulty high pressure sensor