Adaptors for Connection of Air Conditioners SiE30-408
214 Appendix
3. Input of temperature settings
Temperature settings corresponding to resistance values in the range of 0 to 135 can be
made.
Caution The resistance values are counted in wiring resistance.
4. Fetch of display signals
Normal operation output terminals (W1 and W2) and malfunction output terminals (W3 and
W4) are used for no-voltage normal contact output.
(Allowable current is 10mA to 3A per contact.)
Caution In order to use power supply of AC220 ~ 240V, keep the power supply cable away from input
wirings.
In order to make temperature settings from both distant and
remote controller, set thisswitch to "Permitted". (Factory set:
Permitted)
Permitted: Use this mode to make temperature settings from
both distant and remote controllers. (Last setting
priority control is enabled.)
Inhibited: Use this mode only to make temperature settings
from the distant control. (No temperature settingsare
enabled from the remote controller.)
NEVER apply voltage to terminals A
+
or A
.
Wiring adaptor
KRP2A61 • 62 • 51 • 52
SS2
Set temp. (°C) 16 17 18 19 20 21 22 23 24
Resistance value
()
0.0~3.4
5.0~
11.6
13.8~
20.0
22.4~
28.4
31.0~
36.4
39.4~
44.8
48.2~
52.8
56.6~
61.2
65.2~
69.4
Set temp. (°C) 25 26 27 28 29 30 31 32
Resistance value
()
73.8~
77.8
82.4~
85.8
91.0~
94.0
99.4~
102.2
108.6~
110.4
117.2~
119.2
125.8~
127.4
134.2~
140.0
(Wiring specifications)
Types of wires...Sheathed vinyl cords or cables
Size of wire...1.25 to 2.00 mm
2
Total length of wiring...70 m at maximum
(Caution) In order to prevent malfunctions, isolate this wiring from the
power lines.
Normal operation output (Ry1)
This output is turned ON while in normal
operation.
Malfunction output (Ry2)
This output is turned ON if the system stops
due to malfunction, an alarm is given, or
transmission between the adapter PC board
and indoor unit malfunctions.
Ry1
Operation display
Power
source
DC24V
AC24V
AC220
~240V
Error display
Wiring adaptor
KRP2A61 • 62 • 51 • 52
Ry2
W1
W2
W3
W4