7.5.3 Collective Operation [Adapter PCB for Remote Control KRP2A Series]
Purposes and
Functions
A maximum of 64 groups can be controlled the operation of "ON / OFF" collectively. (For the
individual control, use the central remote controller or the unified On / Off controller.)
Cautions: 1. Adapter PCB can be installed in any unit connected to the central transmission line.
2. It cannot be used with other central controller.
3. The setting of group number is not required.
4. The HRV unit judges the ventilation mode individually.
Example Control
Wiring
Switch Setting of
the HRV Unit
The initial setting is required by the remote controller for the indoor unit or HRV unit.
Collective zone interlock setting. . . . . . . . . . . . . . . . . . . . "OFF" (as per factory setting)
The setting of switch on the PCB
Voltage / no-voltage changeover switch(SS1) . . . . . . . . . "no-voltage"
* Remote control mode changeover switch (RS1) should be selected.
Optional
Accessories
Required
Adapter PCB for remote control KRP2A61
B1 B2 BC
W1 W2 W3 W4
X9A
X10A
X11A
J1 J2
X18A
F1 F2
P1P2
P1P2
JC
SS1
F1 F2
P1P2
P1P2
X9A
X10A
X11A
J1 J2 F1 F2
P1P2
JC
SS1
F1 F2
P1P2
P1P2
Indoor unit
HRV unit
Indoor unit
HRV unit
(HC0038)
Connecting line can be
extended up to 150 m
maximum.
Remote control board
(local supply)
ON / OFF
No-voltage normally
open contact for
micro-current
Remote controller
for HRV unit
PCB board KRP2A series
(installed in the indoor
unit)