Daikin REYQ8MY1B [114/206] Nr name description

Daikin REYQ8MY1B [114/206] Nr name description
• Четырехпоточный блок кассетного типа c круговым потоком • FXFQ-P
Системы VRVII, VRVIII Внутренние блоки
113
3 Габаритные и установочные размеры
3.1 Чертеж в масштабе
FXFQ20,25,32,40,50,63P
3D057035
Nr Name Description
1 Indoor unit
2 Decoration panel
3 Suction chamber
4 Connecting chamber (Right)
5 Connecting chamber (Left)
Service acces panel:
450x450 mm or more
NOTES
1 When installing this kit, inspection hatch is necessary.
(It is necessary when servicing.) Either one of
inspection hatches must be installed.
2 Field construction.
3 The corner air outlet of this part must be shut.
4 In case of mounting a duct fan, make sure to
use a wiring adapter for electrical appendices
and link with the indoor unit fan.
5 The intake air flow rate is recommended to be 20%
or less of the H speed air flow rate.
If the intake air flow rate is too large, the operating
sound may rise or detection of the indoor unit suction
temperature may be affected.
6 It indicates the distance between the T-tube inlet and the
indoor unit inlet when the T-tube is connected.
(Refer to note: 1)
Service acces panel:
450 x 450 mm or more
(Refer to note: 1)
Installation service access panel
Pipe connection side
Drain connection side
Note: 3
Note: 3
Inlet
T-tube
Field supply
Air flow rate (m
3
/min)
Ventilation resistance in chamber (Note: 6)
Static pressure of chamber (Pa)
Connecting chamber mounting space
455 (Ceiling opening space)
view
(1000)
FXFQ125P
3TW28914-1
Nr Name Description
1 Liquid pipe connection ø9.52 flare connection
2 Gas pipe connection ø15.90 flare connection
3 Drain pipe connection VP25 (O.D. ø32, I.D. ø25)
4 Power supply connection
5 Transmission wiring connection
6 Air discharge opening
7 Air suction grill
8 Corner decoration cover
9 Drain house O.D. ø32 I.D. ø26
View A
NOTES
1 Location of the nameplates:
- Unit body: on the control box cover.
- Decoration panel: on the panel frame at the motor side
under the corner cover
2 When installing an optional accessory, refer to the installation drawings
- For the fresh air intake kit ... an inspection port is necessary
Drain side
Piping side
See note 3
860 ~ 910 (Ceiling opening)
710 (Suspension position)
See note 4
860 - 910 (Ceiling opening)
780 (Suspension position)
See note 4
See note 4
950
950
420
420
55
55840
340
280
330
Hanging bolt
4 x M8-M10
50
40
285
10
850
Adjustable (0~675)
295
165
175
125
35
35
55
840
130
1500 or more
(Installation space)
200 mm
or more
1500 mm
or more (*)
1500 mm
or more (*)
1500 mm
or more (*)
200 mm
or more
Ventilator Other unit
External surface
light
1500 or more
2000 or more
4000 or more
3 In case of using an Infrared remote control, this position will be a signal receiver.
Refer to the drawing of the infrared remote control for more detail
4 Make sure the spacing between the ceiling and the cassette is no more than 35 mm. Max ceiling opening: 910 mm.
5 When the conditions exceed 30°C and RH 80% in the ceiling or fresh air is inducted into the ceiling, an additional
insulation is required (polyethylene foam, thickness 10 mm or more.)
6 Please respect the distances as shown above
(*) In case a discharge opening is closed with the ‘sealing member’ option, the distance of 1500 mm can be reduced to 500 mm on the closed side.
300 or less
1500 mm
or more (*)
55
Tech Catalogue 2007.indb 113Tech Catalogue 2007.indb 113 17.05.2007 15:44:0517.05.2007 15:44:05