Installation manual
7
RXQ5~10 + RXYQ5~48M9W1B
VRVII System air conditioner
4PW21816-1A
Change as shown in the figure below
3. If the piping length between the outdoor unit-connecting pipe kits or
between the outdoor units exceeds 2 m, create a rise of 200 mm or
more in the gas line within a length of 2 m from the kit.
If 2 m
If 2 m
A Unit A
B Unit B
C Unit C
X Not allowed
O Allowed
1 To indoor unit
2 Oil collects to the stopping outdoor unit.
3 Oil collects to the outdoor unit C when the system stops.
1 To indoor unit
2 Piping between outdoor units
1 To indoor unit
2 Piping between outdoor units
1
1
200 mm
1
2 m
2
1
1
2
2 2
2 m
2 m 2 m
2 m
200 mm
200 mm
200 mm