Daikin RXYQ36M9W1B [26/28] Disposal requirements

Daikin RXYQ8M9W1B [26/28] Disposal requirements
Installation manual
21
RXQ5~10 + RXYQ5~48M9W1B
VRVII System air conditioner
4PW21816-1A
2 Calculate the smallest room volume (m
3
)
In a case such as the following, calculate the volume of (A), (B)
as a single room or as the smallest room.
3 Calculating the refrigerant density using the results of the
calculations in steps 1 and 2 above.
If the result of the above calculation exceeds the maximum
concentration level then make similar calculations for the second
then third smallest room and so until the result falls short of the
maximum concentration.
4 Dealing with the situations where the result exceeds the
maximum concentration level.
Where the installation of a facility results in a concentration in
excess of the maximum concentration level then it will be
necessary to revise the system.
Please consult your supplier.
11.DISPOSAL REQUIREMENTS
Dismantling of the unit, treatment of the refrigerant, oil and eventual
other parts, should be done in accordance with the relevant local and
national regulations.
NOTES
A. Where there are no smaller room divisions
B. Where there is a room division but there is an
opening between the rooms sufficiently large to
permit a free flow of air back and forth.
1
opening between rooms
2
partition
(Where there is an opening without a door or where there are
openings above and below the door which are each equivalent in
size to 0.15% or more of the floor area.)
total volume of
refrigerant in the
refrigerant system
size (m
3
) of smallest
room in which there is
an indoor unit installed
maximum concentration level (kg/m
3
)
1
2