Daikin RXQ5PY1 [35/38] Central remote controller

Daikin RXQ5PY1 [35/38] Central remote controller
6867
SPECIFICATIONS
Note:
1. Cooling and heating capacities are based on the following conditions. Fan is based on High and Ultra-high.
The figures in the parenthesis indicate the heat reclaimed from the heat recovery ventilator.
When calculating the capacity as indoor units, use the following figures:
VKM50GAMV1/GV1: 3.5 kW, VKM80GAMV1/GV1: 5.6 kW, VKM100GAMV1/GV1: 7.0 kW
2. Indoor temperature: 27°C DB, 19°C WB, Outdoor temperature: 35°C DB
3. Indoor temperature: 20°C DB, Outdoor temperature: 7°C DB, 6°C WB
4. Humidifying capacity is based on the following conditions:
Indoor temperature: 20°C DB, 15°C WB, Outdoor temperature: 7°C DB, 6°C WB
5. The operating sound measured at the point 1.5 m below the centre of the unit is converted to that measured
in an anechoic chambar built in accordance with the JIS C 1502 conditions. The actual operating sound
varies depending on the surrounding conditions (near running unit’s sound, reflected sound and so on) and
is normally higher than this value.
For operation in a quiet room, it is required to take measures to lower the sound.
For details, refer to the Engineering Data.
6. The noise level at the air discharge port is about 8–11 dB or higher than the unit’s operating sound.
For operation in a quiet room, it is required to take measures to lower the sound.
7. Air flow rate can be changed over to Low mode or High mode.
8. In case of holding full water in humidifier.
9. OA: fresh air from outdoor. RA: return air from room.
10. Specifications, design and information here are subject to change without notice.
11. Power consumption and efficiency depend on the above value of air flow rate.
12. Temperature exchange efficiency is the mean value for Cooling and Heating. Efficiency is measured under the
following condition: Ratio of rated external static pressure outdoor to indoor is kept constant at 7 to 1.
13. In heating operation, freezing of the outdoor unit’s coil increases. Heating capability decreases and the
system goes into defrost operation. During defrost operation, the fans of the unit continues driving
(factory setting). The purpose of this is to maintain the amount of ventilation and humidifying.
14. When connecting with a VRV system heat recovery type outdoor unit and bringing the RA (exhaust gas
intake) of this unit directly in from the ceiling, connect to a BS unit identical to the VRV indoor unit (master
unit), and use group-linked operation. (See the Engineering Data for details.)
15 When connecting the indoor unit directly to the duct, always use the same system on the indoor unit as
with the outdoor unit, perform group-linked operation, and make the direct duct connection settings from
the remote controller. (Mode No. “17 (27)” – First code No. “5” – Second code No. “6”.) Also, do not
connect to the outlet side of the indoor unit. Depending on the fan strength and static pressure, the unit
might back up.
Feed clean water (city water, tap water or equivalent). Dirty water may clog the
valve or cause dirt deposits in the water container, resulting in poor humidifier performance. (Never use
any cooling tower water and heating-purpose water.)
Also, if the supply water is hard water, use a water softener because of short life.
* Life of humidifying element is about 3 years (4,000 hours) under the supply water conditions of
hardness: 150 mg/l. (Life of humidifying element is about 1 year
(1,500 hours) under the supply water conditions of hardness: 400 mg/l.)
Annual operating hours: 10 hours/day x 26 days/month x 5 months = 1,300 hours
Type
VKM50GAMV1 VKM80GAMV1 VKM100GAMV1
VKM50GAV1 VKM80GAV1 VKM100GAV1
Refrigerant R410A
Power Supply 1 phase, 220–240 V, 50 Hz
Air Flow Rate & Static
Pressure (Note 7)
Ultra-high
Air flow rate (m
3
/h)
500 750 950
Static pressure (Pa)
160 140 110
High
Air flow rate (m
3
/h)
500 750 950
Static pressure (Pa)
120 90 70
Low
Heat
exchange
mode
Bypass
mode
Heat
exchange
mode
Bypass
mode
Air flow rate (m
3
/h)
440 640 820
Static pressure (Pa)
100 70 60
560
490
420
560
490
420
620
560
470
620
560
470
670
570
480
670
570
480
Fan Motor Type Sirroco Fan
Motor Output kW 0.280 × 2 0.280 × 2 0.280 × 2
Sound Level (Note 5)
(220/230/240 V)
Ultra-high (dB)
37/37.5/38
35/35.5/36
32/33/34
37/37.5/38
35/35.5/36
32/33/34
38.5/39/40
36/37/37.5
33/34/35.5
38.5/39/40
36/37/37.5
33/34/35.5
39/39.5/40
37/37.5/38
34/34.5/35.5
39/39.5/40
37/37.5/38
34/34.5/35.5
High (dB)
Low (dB)
Ultra-high (dB)
High (dB)
Low (dB)
Humidification Capacity (Note 4) (kg/h) 2.7 4.0 5.4
Temp. Exchange
Efficiency
Ultra-high (%) 76 78 74
High (%) 76 78 74
Low (%) 77.5 79 76.5
Enthalpy Exchange
Efficiency (Cooling)
Ultra-high (%) 64 66 62
High (%) 64 66 62
Low (%) 67 68 66
Enthalpy Exchange
Efficiency (Heating)
Ultra-high (%) 67 71 65
High (%) 67 71 65
Low (%) 69 73 69
Casing Galvanised Steel Plate
Insulating Material Self-Extinguishable Urethane Foam
Heat Exchanging System Air to Air Cross Flow Tot al Heat (Sensible + Latent Heat) Exchange
Heat Exchanger Element Specially Processed Nonflammable Paper
Air Filter Multidirectional Fibrous Fleece
0°C–40°C DB, 80%RH or less
-15°C–40°C DB, 80%RH or less
0°C–40°C DB, 80%RH or less
s
DX-coil
Capacity
Cooling (Note 2) (kW)
Heating (Note 3) (kW)
Dimensions
Height (mm) 387 387 387
Width (mm) 1,764 1,764 1,764
Depth (mm) 832 1,214 1,214
500
180
500
150
440
110
560
490
420
560
490
420
0.280 × 2
38/38.5/39
36/36.5/37
33.5/34.5/35.5
38/38.5/39
36/36.5/37
33.5/34.5/35.5
76
76
77.5
64
64
67
67
67
69
750
170
750
120
640
80
620
560
470
620
560
470
0.280 × 2
40/41/41.5
37.5/38/39
34.5/36/37
40/41/41.5
37.5/38/39
34.5/36/37
78
78
79
66
66
68
71
71
73
950
150
950
100
820
70
670
570
480
670
570
480
0.280 × 2
40/40.5/41
38/38.5/39
35/36/36.5
40/40.5/41
38/38.5/39
35/36/36.5
74
74
76.5
62
62
66
65
65
69
2.8
3.2
387
1,764
832
96
2.8
3.2
4.5
5.0
5.6
6.4
4.5
5.0
387
1,764
1,214
109
5.6
6.4
387
1,764
1,214
114
Machine Weight
Net (kg)
Gross
(Note 8)
(kg)
102
107
120
129
125
134
Around Unit
OA (Note 9)
RA (Note 9)
Unit Ambient Condition
RXYQ5–54PY1, RXYQ16–50PHY1
Connectable outdoor units
(mm)
Connection Duct Diameter ø200 ø250 ø200 ø250
Ultra-high (W)
High (W)
Low (W)
Power Consumption
Ultra-high (W)
High (W)
Low (W)
• Conforms to CE standards only.
DIMENSIONS
4-14 x 40 oval hole
Hanger bracket
Supply air to room
SA
Return air from room
RA
(For humidifier) *
1
Maintenance cover
(Natural evaporative type)
*
1
Humidifier
Solenoid valve
*
1
EA
(Outdoor air)
Fresh air from outdoors
Exhaust air to outdoors
OA
Control box
Maintenance Cover
More than 600
hatch
Inspection
hatch
Inspection
the air filters, fans (and humidifier)
Maintenance space for the heat exchanger elements
140 (In case of
600 inspection hatch)
360 (In case of
450 inspection hatch)
High efficiency filter (option)
Liquid pipe connection
Air filters
(PT3/4 male screw)
(ø12.7)
(ø6.4)
connection
Gas pipe
Heat exchanger
elements
Drain outlet
(ø6.4C1220T)
Feed water connection port
*
1
of the heat exchanger elements.
Note *1. VKM50/80/100GAMV1 only.
The high effciency filter (option) can be attached to the SA surface*
(
450 or
600) at the service side of filters and elements.
Be sure to provide two inspection hatch.*
Specifications are subject to change without notice.*
VKM50/80/100GA(M)V1
210
B
42
Supply air fan
160
250150
153
C
Damper plate
210
G
K
1688
387
235
60
10
I
20
153
F
Feed water tank *
1
D
130
E
160
144
A
28
102
Direct expansion coil
34
H
J
322
20
1764
515
Exhaust air fan
94
VKM50GA(M)V1
VKM80/100GA(M)V1
832A 1,214
248B 439
431C 622
164D 183
420E 592
248F 439
878G 1,262
137H 89
137I 89
ø196J ø246
ø250K ø263
For wiring
Central remote controller
Remote controller
Wiring adaptor for electrical
appendices
Type
(indoor unit of VRV)
Installation box for adaptor PCB
Unified ON/OFF controller
Schedule timer
For humidifier running ON signal output
For heater control kit
BRC1C62
*1
DCS302CA61
DCS301BA61
DST301BA61
KRP2A61
KRP50-2
BRP4A50
Member
Applicable model
Controlling device
PC Board Adaptor
Centralised
controlling
device
Note: 1.
2.
3.
4.
Installation box is necessary for each adaptor marked .
Up to 2 adaptors can be fixed for each installation box.
Only one installation box can be installed for each indoor unit.
Up to 2 installation boxes can be installed for each indoor unit.
5.
6.
7.
Installation box is necessary for second adaptor.
Installation box is necessary for each adaptor.
*1 Necessary when operating HRV (VKM) independently. When operating interlocked
with other air conditioners, use the remote controllers of the air conditioners.
VKM50/80/100GA(M)V1
Silencer
Air suction/
Discharge grille
High efficiency filter
Flexible duct (1 m)
Flexible duct (2 m)
VKM50GA(M)V1 VKM80GA(M)V1 VKM100GA(M)V1
KDDM24B100
250 mm
K-DGL200B
K-DGL250B
200 250
KAF241G80M KAF241G100M
Air filter for replacement
KAF242G80M KAF242G100M
K-FDS201C K-FDS251C
K-FDS202C K-FDS252C
Nominal pipe diameter (mm)
White
Nominal pipe diameter (mm)
Member
Applicable model
Additional function
OPTIONS
Air Treatment Equipment Lineup
FXCQ-M FXKQ-MAFXFQ-M FXSQ-M FXHQ-MA FXAQ-MA
FXLQ-MA
FXNQ-MA
FXMQ-MA
KRP1B61 KRP1B59
KRP1B61
Notes 2, 3
KRP1B96
Notes 2, 3
KRP1D98
FXZQ-M8
KRP1B57
Notes 4, 6
KRP1B101
Note 5
KRP4A91
FXDYQ-M
KRP1B3
FXUQ-MA
KRP1B97
Notes 2, 3
KRP4A93
Note 3
KRP1C93
KRP1B61
FXDQ-P
FXDQ-NA
Notes 4, 6
KRP1B101
KRP1B56