Daikin RXQ5PY1 [37/38] Vam150gjve vam250gjve vam350gjve vam500gjve

Daikin RXYQ20PY1 [37/38] Vam150gjve vam250gjve vam350gjve vam500gjve
7271
Note: 1.
2.
3.
4.
5.
6.
7.
8.
9.
10
.
11
.
Sound level is measured at 1.5m below the centre of the body.
Air flow rate can be changed over to Low mode or High mode.
Sound level is measured in an anechoic chamber.
Sound level generally becomes greater than this value depending on the operating conditions, reflected sound, and peripheral noise.
The sound level at the air discharge port is about 8 dB higher than the unit's sound level.
The specifications, designs and information given here are subject to change without notice.
Temperature Exchange Efficiency is the mean value between cooling and heating.
Efficiency is measured under the following conditions:
Ratio of rated external static pressure has been maintained as follows; outdoor side to indoor side = 7 to 1.
In conformance with JIS standards (JIS B 8628), operating sound level is based on the value when one unit is operated, with the value converted for an anechoic chamber. This is
transmission sound from the main unit, and does not include sound from the discharge grille. Thus it is normal for the sound to be louder than the indicated value when the unit is
actually installed.
Sound level from the discharge port causes the value to be approximately 8 dB (models with the air flow rate of less than 150 to 500 m
3
/h) to approximately 11 dB (models with the air
flow rate of 650 m
3
/h or more) greater than the indicated value. Furthermore, fan rotation and noise from the discharge grille may increase depending on the on-site duct resistance
conditions. Please consider noise countermeasures when installing the unit.
With large models in particular (1500 and 2000 m
3
/h models), if the supply air (SA) grille is installed near the main unit, the noise of the main unit may be heard from the discharge
grille via the duct, and this will result in a marked increase in noise. In such cases, if peripheral effects are included (such as reverberation of the floor and walls, combination with
other equipment, and background noise), sound level may be as much as 15 dB higher than the indicated value. When installing a large model, please provide as much separation as
possible between the main unit and the discharge grille. If the equipment and discharge grille are near each other, please consider countermeasures such as the following:
•Use a sound-muffling box, flexible duct and sound-muffling air supply/discharge grilles
•Decentralised installation of discharge grilles
When installing in a location with particularly low background noise such as a classroom, please consider the following measures to avoid transmission sound from the main unit:
•Use of ceiling materials with high sound insulating properties (high transmission loss)
•Methods of blocking sound transmission, for example, by adding sound insulating materials around the bottom of the sound source.
Alternatively, consider supplementary methods such as installing the equipment in a different location (corridor, etc.)
Models
VAM150GJVE VAM250GJVE VAM350GJVE VAM500GJVE
Temp. Exchange
Efficiency (%)
[50Hz/60Hz]
Ultra-High
High
84/85 79/79
79/79 75/75
79/79 75/75
79/79 74/74
79/79 74/74
75/75 72/72
75/75 72/72
78/78 72/72
78/78 72/72
77/77
77/77
82/82 80/80.5
For Heating
Enthalpy
Exchange
Efficiency (%)
[50Hz/60Hz]
For Cooling
Low
72/72 71/71 70/70 67/67
Ultra-High
72/72 71/71 70/70 67/67High
76/76.5 74/74 77/77 74/74.5Low
66/66 63/63 66/66 55/55
Ultra-High
66/66 63/63 66/66 55/55High
70/70.5 66/66 70/70 59/59.5Low
Heat
Exchange
Mode
Sound Level
dB(A)
[50Hz/60Hz]
Bypass
Mode
27-28.5/28.5 27-29/29 31.5-33/33 33-35.5/34
Ultra-High
26-27.5/27.5 26-27.5/28 30-31.5/30 31.5-34/32High
20.5-21.5/21 21-22/21 23-25/23 25-28.5/24Low
28.5-29.5/29.5 28.5-30.5/30.5
33-34.5/34.5 34.5-36/35.5
Ultra-High
27.5-28.5/28.5
27.5-29/29.5 31.5-33/31.5 33-34.5/33.5High
22.5-23.5/22
Galvanised steel plate
22.5-23/22.5
24.5-26.5/24.5
25.5-28.5/25.5
Low
150/150 250/250 350/350 500/500
Ultra-High
150/150 250/250 350/350 500/500High
100/95 155/155 230/230 320/295Low
278
X
810
X
551 306
X
879
X
800mm
24 32kg
Casing
VE: 1 phase, 220-240V/ 220V,50Hz/ 60HzPower Supply
Self-extinguishable polyurethane foamInsulation Material
Air to air cross flow total heat (Sensible heat + latent heat) exchangeHeat Exchange System
Specially processed nonflammable paperHeat Exchange Element Material
Multidirectional fibrous fleecesAir Filter
Sirroco fanType
Fan
Dimensions (H
X
W
X
D)
Weight
0.030
X
2 0.090
X
2kW
100 150 200mm
-15°C~+50°CDB, 80%RH or lessUnit ambient condition
Motor Output
Connection Duct Diameter
Air Flow Rate (m
3
/h)
[50Hz/60Hz]
120/154 70/96 169/222 105/150
Ultra-High
106/131 54/65 141/145 66/52High
56/60 24/20 67/30 32/18Low
External Static
Pressure (Pa)
[50Hz/60Hz]
VAM650GJVE VAM800GJVE
VAM1000
GJVE
VAM1500
GJVE
77/77.5 74/74.5 80.5/81 75.5/76
67.5/67.5 65/65 70/70 65/65
67.5/67.5 65/65 70/70 65/65
71.5/72 67.5/68 72.5/73 67/67.5
61/61 61/61 64/64 61/61
61/61 61/61 64/64 61/61
64/64.5 64/64.5 68.5/69 64/64.5
34-36/36 39-40.5/39.5
39.5-41.5/39.5 39.5-41.5/41.5
33-34.5/34 37-39.5/37.5
37.5-39.5/37.5 37.5-39.5/39.5
27.5-29.5/28 35-37.5/34 35-37.5/34.5 35-37.5/36
35-37.5/37.5
40.5-42/41
40.5-42.5/40.5
41-43/42.5
33-35.5/35.5 38.5-40/39
38.5-40.5/38.5
39.5-41/41.5
27.5-30.5/29.5
36-38.5/35.5 36-38.5/35.5 36.5-38/37.5
650/650 800/800 1,000/1,000 1,500/1,500
650/650 800/800 1,000/1,000 1,500/1,500
500/470 700/670 860/840 1,320/1,260
387
X
1,111
X
1,214387
X
1,111
X
832
338
X
973
X
832
45 55 67
785
X
1,619
X
832 785
X
1,619
X
1,214
129
0.140
X
2 0.280
X
2 0.280
X
4
250 350
85/125 133/170 168/192 112/150
53/67 92/85 110/86 73/72
35/38 72/61 85/60 56/50
VAM2000
GJVE
79/81
72/72
72/72
75/76
62/62
62/62
66/67
41.5-43.5/42
39-43/40
36-39/39
43-45.5/44
40.5-45/42
37.5-39.5/41
2,000/2,000
2,000/2,000
1,720/1,580
157
116/140
58/32
45/45
For wiring
Option List
Silencer
VAM150GJVE VAM250GJVE VAM350GJVE VAM500GJVE VAM650GJVE VAM800GJVE
VAM1000GJVE VAM1500GJVE VAM2000GJVE
KDDM24B50
KDDM24B100 KDDM24A100
X
2
200 250
Air suction/discharge grille (Field supply)
Branch duct
(Field supply)
SA
SA
RA
EA
OA
Duct
(Field supply)
Flexible duct
(Option)
Silencer (Option)
Round hood
(Field supply)
Thermal insulation material (Field supply)
High efficient filter
(Option)
Nominal pipe diameter (mm)
Member
Applicable model
Additional
function
Central remote controller
HRV remote controller
Wiring adaptor for electrical
appendices
Installation box for adaptor PCB
Type
(indoor unit of VRV)
Installation box for adaptor PCB
Unified ON/OFF controller
Schedule timer
For humidifier
For heater control kit
BRC301B61
DCS302CA61
DCS301BA61
DST301BA61
KRP2A61
KRP50-2
BRP4A50
KRP50-2A90 (Mounted electric component assy of HRV)
Member
Applicable model
Controlling device
PC Board Adaptor
Centralised
controlling
device
Note: 1.
2.
3.
Installation box is necessary for each adaptor marked .
Up to 2 adaptors can be fixed for each installation box.
Only one installation box can be installed for each indoor unit.
High efficiency filter
Flexible duct (1m)
Flexible duct (2m)
Duct adaptor
KAF242G25M KAF242G50M KAF242G65M KAF242G80M
KAF241G65M KAF241G80M
KAF242G100M
KAF242G80M
X
2
KAF242G100M
X
2
Air filter for replacement
KAF241G25M KAF241G50M
KAF241G100M
KAF241G80M
X
2
KAF241G100M
X
2
K-FDS101C
K-FDS151C K-FDS201C K-FDS251C
K-FDS102C
K-FDS152C K-FDS202C K-FDS252C
YDFA25A1
250
Nominal pipe diameter (mm)
4.
5.
6.
Up to 2 installation boxes can be installed for each indoor unit.
Installation box is necessary for second adaptor.
Installation box is necessary for each adaptor.
SPECIFICATIONS OPTIONS
Air Treatment Equipment Lineup
EA
OA
RA
SA
Power supply (Field supply)
Relay box
Temperature thermo.
(Field supply)
(ON when the temperature
is at or below -10°C)
HRV
Heater
control kit
(Field supply)
BRP4A50
Temperature thermo. (Field supply)
(OFF when the temperature is at or more than 5°C)
Indoor Outdoor
When the installation of an electric heater is required in a cold region, this adaptor with an internal timer function eliminates the
complicated timer connecting work that was necessary with conventional heaters.
Examine fully an installation place and
specification for using the electric heater based on
the standard and regulation of each country.
Supply the electric heater and safety production
devices such as a relay and a thermostat, etc of
which qualities satisfy the standerd and regulation
of each country at site.
Use a non-inflammable connecting duct to the
electric heater. Be sure to allow 2 m or more
between the electric heater and HRV for safty.
For the HRV units, use a different power supply
from that of the electric heater and install a circuit
breaker for each.
Notes when installing
PC board adaptor for heater control kit (BRP4A50)
FXCQ-M FXKQ-MAFXZQ-M8 FXSQ-M FXHQ-MA FXAQ-MA
FXLQ-MA
FXNQ-MA
FXMQ-MA
KRP1B61 KRP1B57 KRP1B61
Note 2, 3
KRP1B96
Note 4, 6
KRP1B101
Note 5
KRP4A91
FXDQ-P
FXDQ-NA
Note 4, 6
KRP1B101
FXDYQ-M
KRP1B3
FXUQ-MA
KRP1B97
Note 2, 3
KRP4A93
Note 3
KRP1C93
KRP1B61KRP1B61 KRP1B56
FXFQ-M
KRP1B59
Note 2, 3
KRP1D98