Daikin RXQ40PAHY1 [11/36] Middle and high static pressure allows for flexible duct design

Daikin RXQ40PAHY1 [11/36] Middle and high static pressure allows for flexible duct design
2019
Indoor Unit Lineup
Slim Ceiling Mounted Duct Type
Slim design, quietness and
static pressure switching
FXDQ20PB/FXDQ25PB/FXDQ32PB
External static pressure selectable by remote
controller switching make this indoor unit a very
comfortable and flexible model.
10 Pa-30 Pa/factory set: 10 Pa for FXDQ-PB models.
15 Pa-44 Pa/factory set: 15 Pa for FXDQ-NB models.
Only 200 mm in height, this model can be
installed in rooms with as little as 240 mm depth
between the drop-ceiling and ceiling slab.
Only 700 mm in width and 23 kg in weight, this
model is suitable to install in limited spaces like
drop-ceilings in hotels.
Low operation sound level
(dB(A))
The values of operation sound level represent those for rear-suction operation.
Sound level values for bottom-suction operation can be obtained by adding 5 dB(A).
Values are based on the following conditions:
FXDQ-PB: external static pressure of 10 Pa; FXDQ-NB: external static pressure of 15 Pa.
1,100 mm in width for the FXDQ63NB model.
200 mm
900 mm
Suction grille*
AIR
AIR
Discharge grille*
Air filter
Suspension bolt*
240 mm
* To be obtained locally
FXDQ-PB and FXDQ-NB models are available in
two types to suit different installation conditions.
FXDQ-PB/NBVE: with a drain pump (750 mm lift)
as a standard accessory
FXDQ-PB/NBVET: without a drain pump
Only 700 mm
200 mm
Great for
hotel use!
Suited to use in drop-ceilings!
750 mm
Ceiling
Control of the airflow rate has been improved
from 2-step to 3-step control.
FXDQ40NB/FXDQ50NB/FXDQ63NB
36/34/32
63
35/33/31
50
34/32/30
40
33/31/29
20/25/32
Sound level
(HH/H/L)
FXDQ-PB/NB
Ceiling Mounted Duct Type
Middle and high static pressure
allows for flexible duct design
FXMQ20P/FXMQ25P/FXMQ32P
FXMQ40P/FXMQ50P/FXMQ63P
FXMQ80P/FXMQ100P/FXMQ125P
FXMQ140P
Built-in Drain Pump (Option)
Housing the drain pump inside the unit reduces the
space required for installation.
All models are only 300 mm in height, an
improvement over the 390 mm height of
conventional models. The weight of the
FXMQ40P has been reduced from 44 kg to 28 kg.
A DC fan motor increases the external static
pressure capacity range to include middle to high
static pressures, increasing design flexibility.
Indoor unit
470
mm
Indoor unit
470
mm
0–250
mm
222
mm
Without drain pump
With drain pump
Simplified Static Pressure Control
External static pressure can be easily adjusted using
a change-over switch inside the electrical box to meet
the resistance in the duct system.
FXMQ200MA/FXMQ250MA
Drain pump is equipped as
standard accessory with
700 mm lift.
Control of the airflow rate has been improved
from 2-step to 3-step control.
(dB(A))
46/45/43
140
42/40/38
63
43/41/39
80/100
41/39/37
50
39/37/35
40
34/32/30
32
33/31/29
20/25
Sound
level
(HH/H/L)
FXMQ-P
700 mm
Ceiling
30 Pa–100 Pa for FXMQ20P-32P
30 Pa–160 Pa for FXMQ40P
50 Pa–200 Pa for FXMQ50P-125P
50 Pa–140 Pa for FXMQ140P
Low operation sound level
Improved ease of installation
Improved ease of maintenance
Airflow rate can be controlled using a remote controller
during test operation. With the conventional model, the
airflow rate was controlled from the PC board. It is
automatically adjusted to the range between approximately
±10% of the rated HH tap airflow for FXMQ20P–125P.
The drain pan can be detached for easy cleaning. An
antibacterial treatment that uses silver ions has been
applied to the drain pan, preventing the growth of slime,
mould and bacteria that cause blockages and odours.
Energy-efficient
The adopted DC fan motor is much more efficient than
the conventional AC motor, yielding an approximate
20% decrease in energy consumption (FXMQ125P).