Daikin RXYQ240PYDN [405/567] Troubleshooting

Daikin RXYQ192PTJU [405/567] Troubleshooting
Troubleshooting by Indication on the Remote Controller SiUS34-801A_b
390 Troubleshooting
Troubleshooting
1: Voltage measurement point
2: Refer to “Pressure Sensor, Pressure / Voltage Characteristics” table on P525.
(V2808)
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Replace the main PC board.
Replace the low pressure sensor.
YES
NO
Replace the main PC board.
NO
Replace the low pressure sensor.
YES
NO
Are
the characteristics
of the low pressure sensor
normal? (Make a comparison
between the voltage characteristics
(1) and the gauge
pressure.)
YES
If
the PC board
pressure detection normal?
(Make a comparison between the
checker pressure data and the
voltage characteristics
(1).)
1.Set the low pressure gauge
upright.
2.Connect the checker for
VRV to the gauge.
Confirm which low pressure
sensor is abnormal using
outdoor unit "monitor mode".
(Refer to Page 334~335)
Reset the operation, and then
restart the outdoor unit.
Are the
characteristics of the low
pressure sensor
normal?