Daikin REYQ96PATJ [20/22] Onsite settings
![Daikin REYQ96PAYD [20/22] Onsite settings](/views2/1718197/page20/bg14.png)
16 English
6.
After completing the additional refrigerant charging, record the charging
amount on the accessory “REQUEST FOR THE INDICATON” label
(Installation records) and adhere it to the back side of the front panel.
11-2-2 Procedure of check operation
• Check operation perform the following work. Do the check operation
following below.
Otherwise, malfunction code “U3” will be displayed in the remote
controller and nomal operation can not be carried out.
Check of shutoff valve opening
Check of miswiring
Judgment of piping length
Check of refrigerant overcharge
NOTE
• Check operation can not carried out at outdoor temp. less than 23°F.
Perform the check operation at day or time that outdoor temp. is 23°F
or more.
[Check Operation Procedure]
(1) Close the EL. COMPO. BOX lid and all front panels except as the
side of the EL. COMPO. BOX and turn on the power to the outside
unit and all connected BS, indoor units. (Be sure to turn the power on
at least 6 hours before operation in order to have power running to
the crank case heater.)
(2) Make the onsite settings as needed using the push button (BS1-
BS5) on the outside unit PC-board (A1P) with the power on. (See
“12 Onsite Settings”)
(3) Perform the check operation following the Check Operation Method
of the [Service Precautions] label (lower) on the EL. COMPO. BOX
lid. (See figure 31) The system operation for about 40~60 minutes
and automatically stops the check operation.
If the malfunction code is not displayed in the remote controller after
the system stop, check operation is completed. Normal operation will
be possible after 5 minutes. If the malfunction code is displayed in the
remote controller, correct the malfunction following [Remote control-
ler displays malfunction code] and perform the check operation again.
(Refer to figure 31)
1. EL. COMPO.BOX (1) lid
2. EL. COMPO.BOX (2) lid
3. [Service Precaution] label (upper)
4. [Service Precaution] label (lower)
NOTE
For interrupting the check operation, push RETURN button (BS3).
[Remote controller displays malfunction code]
NOTE
If any malfunction codes other than the above are displayed, check the
service manual for how to respond.
12. ONSITE SETTINGS
NOTE
In the case of a multi system, all onsite settings should be made on the
master unit. Settings made on sub units are invalid.
The outside unit to which the indoor unit transmission wire are con-
nected is the master unit, and all other units are sub units.
Use the push button switches (BS1 through BS5) on the outside unit
PC-board (A1P) to make the necessary onsite settings.
See the “Service Precautions” label (upper) on the EL. CONPO. BOX lid
for details on the positions and operating method of the push button
switches and on the onsite setting.
Make sure to record the setting on the accessory “REQUEST FOR THE
INDICATION” label.
WARNING Electric Shock Warning
Use an insulated rod to operate the push buttons via the inspection door
of EL. COMPO. BOX lid.
There is a risk of electric shock if you touch any live parts, since this
operation must be performed with the power on.
13. TEST RUN
13-1 Before test run
• Make sure the following works are completed in accordance with the
installation manual.
Piping work
Wiring work
Air tight test
Vacuum drying
Additional refrigerant charge
Check operation
• Check that all work for the BS, indoor unit are finished and there are
no danger to operate.
13-2 Test Run
After all works are completed, operate the unit normally and check the
following.
(1) Make sure the indoor and outside units are operating normally.
(2) Operate each indoor unit one by one and make sure the correspond-
ing outside unit is also operating.
(3) Check to see if cold (or hot) air is coming out from the indoor unit.
(4) Push the fan direction and strength buttons on the remote controller
to see if they operate properly.
NOTE
• Heating is not possible if the outdoor temperature is 75°F or higher.
Refer to the Operation manual.
• If a knocking sound can be heard in the liquid compression of the com-
pressor, stop the unit immediately and then energize the crank case
heater for a sufficient length of time before restarting the operation.
• Once stopping, the compressor will not restart in about 5 minutes
even if the On/Off button of the remote controller is pushed.
• When the system operation is stopped by the remote controller, the out-
side units may continue operating for further 5 minutes at maximum.
• The outside unit fan may rotate at low speeds if the Night-time low
noise setting or the External low noise level setting is made, but this
is not a malfunction.
Malfunc-
tion code
Installation error Remedial action
E3, E4
F3, F6
UF
The shutoff valve of the outside
unit is left closed.
Open the shutoff valve.
U1
The phases of the power to
the outside unit is reversed.
Exchange two of the three phases (L1,
L2, L3) to make a proper connection.
U1
U4
LC
No power is supplied to an
outside, BS or indoor unit
(including phase interruption).
Make sure the power source wire is
properly connected to the outside, BS or
indoor unit and revise if necessary.
UF
There is conflict on the con-
nection of transmission wir-
ing in the system.
Check if the refrigerant piping line and
the transmission wiring are consistent
with each other.
E3
F6
UF
Refrigerant overcharge.
Recalculate the additional amount refrig-
erant from the piping length and correct
the refrigerant charge level by recovering
any excessive refrigerant with a refriger-
ant recovery machine.
E4
F3
Insufficient refrigerant.
•
Check if the additional refrigerant
charge has been finished correctly.
•
Recalculate the additional amount
refrigerant from the piping length and
add the adequate amount.
U7, U4
UF, UH
Field wiring is connected to "TO
MULTI UNIT (Q1,Q2)" terminal
on the outside unit PC-board
(A1P) when the system is one
outdoor system.
Remove the line from the “TO MULTI UNIT
(Q1, Q2)” terminal.
Содержание
- Installation manual 1
- System air conditioner 1
- Figure 1 figure 3 figure 2 2
- Figure 11 2
- Figure 12 2
- Figure 4 figure 6 figure 5 2
- Figure 7 figure 8 figure 9 figure 10 2
- Figure 13 figure 14 3
- Figure 15 3
- Figure 16 figure 17 2 3
- Figure 17 1 3
- Figure 18 3
- Figure 19 3
- Figure 20 figure 22 3
- Figure 21 3
- Figure 23 4
- Figure 24 4
- Figure 25 4
- Figure 26 4
- Figure 27 figure 29 4
- Figure 28 4
- Figure 30 4
- Figure 31 4
- 1 safety considerations 5
- Contents 5
- English 1 5
- First of all 5
- 2 special notice of product 6
- English 6
- 1 combination 7
- 2 standard supplied accessories 7
- 3 disposal requirements 7
- 3 option accessory 7
- 4 technical and electrical specifications 7
- 5 main components 7
- English 3 7
- Introduction 7
- Selection of location 7
- 1 selection of piping material and refrigerant branching kit 8
- 1 selection of piping material and refrigerantbranching kit 8
- English 8
- Inspecting and handling the unit 8
- Placing the unit 8
- Refrigerant piping 8
- 2 protection against contamination when installing pipes 9
- 2 protection against contaminationwhen installing pipes 9
- 3 pipe connection 9
- 4 connecting the refrigerant piping 9
- English 5 9
- 1 indicate the outside unit multi connection piping kit 2 in case of multi outdoor system re read outside unit to the first outside unit multi connection piping kit as seen from the indoor unit 10
- 5 example of connection 10
- Actual and equivalent pipe length 10
- Actual pipe length 10
- Actual pipe length equivalent length 10
- Actual pipe length from first refrigerant branch kit either refnet joint or refnet header to indoor unit 130 ft note 2 example 8 b c d e s 130 ft 10
- Allowable length after the branch 10
- Between outside unit 2 and indoor unit 10
- Bold 3 pipes 10
- Branch with refnet joint branch with refnet joint and header branch with refnet header 10
- Bs unit 10
- Difference in height between outside unit and indoor unit h1 164 ft max 130 ft if the outside unit is below difference in height between adjacent indoor units h2 49 ft difference in height between adjacent outside units h3 16 ft 10
- English 10
- Example 6 b 130 ft 8 m n p 130 ft example 8 o 10
- Example 8 a o 10
- Example of connection connection of 8 indoor units 10
- First outside unit multi connection piping kit 10
- Ft equivalent pipe length between outside unit 2 and indoor unit 620 ft note 1 10
- Indoor unit cool heat selection possible 10
- Indoor unit cooling only 10
- Indoor unit side 2 pipes 10
- Multi outside system 10
- Outside unit 10
- Outside unit outside unit 10
- Outside unit side 3 pipes 10
- Pipe length between outside unit 2 and indoor unit 540 ft example 8 a b c d e 540 ft 10
- Piping from bs unit to indoor unit or piping from refrigerant branch kit to indoor unit used as cooling only 10
- Piping from outside unit to bs unit 10
- Single outside system 10
- Suction gas pipe hp lp gas pipe liquid pipe 10
- Suction gas pipe liquid pipe 10
- Thin 2 pipes 10
- Total piping length from outside unit 2 to all indoor unit 3280 ft actual pipe length from first outside unit multi connection piping kit to outside unit 33 ft equivalent pipe length from first outside unit multi connection piping kit to outside unit 43 ft 10
- English 7 11
- Outside unit multi connection piping kit and refrigerant branch kit selection 11
- Pipe size selection 11
- 0 75 1 0 21 1 0 81 75 0 40 10 0 15 1 2 2 1 12
- 11 82 11 lb 12
- A b 2 c 2 d 2 e 2 f 2 g 2 h i j k l m n p 3280 ft 12
- A b u r c n s t o p 12
- English 12
- How to calculate the additional refrigerant to be charged 12
- If available on the site use this size otherwise it can not be increased 12
- Increase the pipe size as follows 12
- Indoor units 1 8 12
- Outside unit refnet joint a g 12
- Required conditions example drawings 12
- Round off in units of 0 lb 12
- The farthest indoor unit 8 the nearest indoor unit 1 12
- Φ 3 8 φ 1 2 φ 1 2 φ 5 8 φ 5 8 φ 3 4 φ 3 4 φ 7 8 φ 7 8 φ 1 φ 1 1 8 φ 1 1 4 φ 1 3 8 φ 1 1 2 12
- 1 power circuit safety device and cable requirements 13
- 1 power circuit safety device and cablerequirements 13
- 2 wiring connection example for whole system 13
- 3 leading wire procedure 13
- English 9 13
- Field wiring 13
- 4 transmission wiring connection procedure 14
- 5 power wiring connection procedure 14
- Crimp style terminal 14
- Cup washer 14
- Cut out section 14
- English 14
- Power wire crimp style terminal 14
- 6 procedure for wiring inside units 15
- Air tight test and vacuum drying 15
- English 11 15
- R410a label 15
- Resin hook 15
- Terminal block crip style terminal wire narrow wire thick 15
- 1 before working 16
- Additional refrigerant charge and check operation 16
- Additional refrigerant chargeand check operation 16
- Checking of device and installa tion conditions 16
- Checking of device and installationconditions 16
- English 16
- Pipe insulation 16
- 2 procedure of adding refrigerant charging and check operation 17
- 2 procedure of adding refrigerant charging andcheck operation 17
- English 13 17
- H h i h h h h 17
- J h h h h h h 17
- J h h h i h i 17
- J h h i h h h 17
- J h j h j j h 17
- 2 1 procedure of adding refrigerant charging 18
- Cooling mode 18
- English 18
- H h i h h h h 18
- Heating mode 18
- Less than above range 18
- Outdoor temp 32 f db 109 f db indoor temp 50 f db 90 f db 18
- English 15 19
- 1 before test run 20
- 2 2 procedure of check operation 20
- 2 test run 20
- English 20
- Onsite settings 20
- Test run 20
- 3 checks after test run 21
- Caution for refrigerant leaks 21
- English 17 21
- P215731 8m em09a062a 22
Похожие устройства
- Daikin REYQ72PATJ Инструкция по монтажу
- Daikin REYQ120PATJ Спецификация
- Daikin REYQ120PATJ Руководство по вводу в эксплуатацию
- Daikin REYQ120PATJ Инструкция по монтажу
- Daikin REYQ120PATJ Инструкция по монтажу
- Daikin REYQ192PATJ Спецификация
- Daikin REYQ168PATJ Спецификация
- Daikin REYQ168PATJ Руководство по вводу в эксплуатацию
- Daikin REYQ192PATJ Руководство по вводу в эксплуатацию
- Daikin REYQ192PATJ Инструкция по монтажу
- Daikin REYQ168PATJ Инструкция по монтажу
- Daikin REYQ144PATJ Спецификация
- Daikin REYQ144PATJ Руководство по вводу в эксплуатацию
- Daikin REYQ144PATJ Инструкция по монтажу
- Daikin REYQ72PAYD Спецификация
- Daikin REYQ72PAYD Руководство по вводу в эксплуатацию
- Daikin REYQ72PAYD Инструкция по монтажу
- Daikin REYQ96PAYD Спецификация
- Daikin REYQ96PAYD Руководство по вводу в эксплуатацию
- Daikin REYQ96PAYD Инструкция по монтажу