Daikin RQYQ16PY1 [17/20] 2 procedure of adding refrigerant charging and check operation

Daikin RQYQ18PY1 [17/20] 2 procedure of adding refrigerant charging and check operation
English 12
11-2 Procedure of Adding Refrigerant charging
and check operation
WARNING ELECTRIC SHOCK WARNING
Make sure to close the EL. COMPO. BOX lid before turning on
the power when performing the refrigerant charging operation.
Perform the setting on the PC-board (A1P) of the outdoor unit and
check the LED display after the power is on via the inspection
door which is in the EL. COMPO. BOX lid.
Use an insulated rod to operate the push buttons via the EL.
COMPO. BOX’s inspection door.
There is a risk of electric shock if you touch any live parts, since
this operation must be performed with the power on.
CAUTION
Make sure to use the protect tool (protective groves and gog-
gles) when charging the refrigerant.
Due to a danger of liquid hammer, the refrigerant must not be
charged over the allowable maximum amount when charging the
refrigerant.
Do not perform the refrigerant charging operation under working
for the indoor unit.
When opening the front panel, make sure to take caution to the fan
rotation during the working.
After the outdoor unit stops operating, the fan may keep rotation
for a while.
Note
If operation is performed within 12 minutes after the indoor and
outdoor units are turned on, H2P will be lit on and the compressor
will not operate.
In order to ensure uniform refrigerant distribution, it may take up to
around 10 minutes for the compressor to start up after the unit
starting operating. This is not a malfunction.
<About refrigerant charging>
The refrigerant charge port is connected to the piping inside the
unit.
When the unit is shipped from the factory, the unit’s internal piping
is already charged with refrigerant, so be careful when connecting
the charge hose.
After adding the refrigerant, make sure to close the lid of the
refrigerant charging port.
The tightening torque for the lid is 11.5 to 13.9 N·m.
See [Shutoff valve operation procedure] in chapter 11-1 for details
on how to handle shutoff valves.
When done or when pausing the refrigerant charging operation,
close the valve of the refrigerant tank immediately. If the tank is
left with the valve open, the amount of refrigerant which is prop-
erly charged may be off the point. More refrigerant may be
charged by any remaining pressure after the machine is stopped.
<About check operation>
Make sure to perform the check operation after installation.
Otherwise, the malfunction code “U3” will be displayed and
normal operation cannot be performed.
And the failure of “Check of miswiring” may also cause abnormal
operation. Performance may drop due to the failure of “Judgment
of piping length”.
Check operation must be performed for each refrigerant piping
system.
Checking is impossible if plural systems are being done at once.
The individual problems of indoor units can not be checked.
About these problems check by test run after the check operation
is completed. (See chapter 13)
The check operation cannot be performed in recovery or other
service modes.
1.
Make sure the following works are complete in accordance with
the installation manual.
Piping work
Wiring work
Air tight test
Vacuum drying
Installation work for indoor unit
2.
Calculate the “additional charging amount” from the following.
3.
Open the valve C (See the figure 31. The valve A, B and the liquid
and gas side shutout valve must be left closed), and charge the
refrigerant of the “additional charging amount” from the liquid side
shutout valve service port.
If the “additional charging amount” was charged fully, close the
valve C and go to step 5.
If the “additional charging amount” was not charged fully, go to
step 4.
(Refer to figure 31)
1. Measuring device
2. R410A tank (with siphon)
3. Charge hose
4. Liquid side shutoff valve
5. Gas side shutoff valve
6. Shutoff valve service port
7. Valve B
8. Valve C
9. Valve A
10. Outdoor unit
11. Refrigerant charge port
12. To indoor unit
13. Field pipings
14. Refrigerant flow
4.
Perform the refrigerant charging operation according to “INSTAL-
LATION MANUAL (2)”, and charge the remaining refrigerant of
the “additional charging amount”. For performing the refrigerant
charging operation the push button on the PC-board (A1P) of out-
door unit (Incase of multi system master unit) are use. (See the
figure 32) In addition, the refrigerant are charged from the refrig-
erant charge port via the valve A. (See the figure 33)
For operating the push button and opening and closing the valve,
follow the work procedure.
Note
The refrigerant will be charged about 22kg in one hour at outdoor
temp. 30°C DB (6kg at 0°C DB).
If you need to speedup in case of multi system, connect the refriger-
ant tanks to each outdoor unit as shown in the figure 33.
(Refer to figure 32)
1. EL.COMPO.BOX lid
2. Pipe intake
3. Inspection door
4. Label “Service Precaution”
5. LED (H1~8P)
6. Push button (BS1-5)
7. Lift the protruding part to open the cover
additional
charge amount
RQYQ8PY1
0.0kg
RQYQ10PY1
0.7kg
RQYQ12PY1
2.1kg
RQYQ14PY1
1.7kg
RQYQ16PY1
2.0kg
RQYQ18PY1
0.7kg
RQYQ20PY1
2.1kg
RQYQ22PY1
2.8kg
RQYQ24PY1
4.2kg
RQYQ26PY1
2.7kg
RQYQ28PY1
4.1kg
RQYQ30PY1
3.7kg
RQYQ32PY1
4.0kg
RQYQ34PY1
2.7kg
RQYQ36PY1
4.1kg
RQYQ38PY1
4.8kg
RQYQ40PY1
6.2kg
RQYQ42PY1
4.7kg
RQYQ44PY1
6.1kg
RQYQ46PY1
5.7kg
RQYQ48PY1
6.0kg

Содержание

Скачать
Случайные обсуждения

Ответы 0

Hi, good afternoon.
1 год назад