Daikin VAM2000GJVE [8/10] Enthalpy exchange efficiency cooling
![Daikin VAM150GJVE [8/10] Enthalpy exchange efficiency cooling](/views2/1719152/page8/bg8.png)
VAM150GJVE
VAM1000GJVE VAM1500GJVE VAM2000GJVE
VAM250GJVE
VAM350GJVE VAM500GJVE
VAM650GJVE VAM800GJVE
13 14
Dimensions
Dimensions
Dimensions
Dimensions
VAM-GJ VE Ser ies
VAM-GJ VE Ser ies
SA: Supply air to room
RA: Return air from room
OA: Fresh air from outdoors (Outdoor air)
EA: Exhaust air to outdoors
High efficiency filter
(Optional accessory)
Maintenance space for the heat exchange
elements, the air filters and fans
150~250
20
(Maintenance cover)
145
Heat exchange elements
275
450
Exhaust air fan
278
600~
Maintenance cover
Air filters
Control box
200
158
68
Inspection hole
754
551
Damper plate
97
121
601
Supply air fan
275
810
150
20
145
Ceiling hook
4-12
X
40 oval hole
(Control box)
126 150
126
109
SA
RA
OA
EA
Remark)
1. Be sure to provide the inspection hole (450
X
450 mm) to inspect the air filters, the exchange elements
and fans.
2. It is possible to install the high efficiency filter on the SA face side of heat exchange element.
121
158
109
High efficiency filter
(Optional accessory)
278
(Maintenance cover)
150
551
146
200
20601
Exhaust air fan
150~250
20
132
275
275
Maintenance space for the heat exchange
elements, the air filters and fans
810
450
(Control box)
Air filters
121
600~
Control box
Ceiling hook
4-12
X
40 oval hole
126
Inspection hole
Maintenance cover
150
132
68
158
Damper plate
126
754
Heat exchange elements
Supply air fan
109
SA
RA
OA
EA
Remark)
1. Be sure to provide the inspection hole (450
X
450 mm) to inspect the air filters, the exchange elements
and fans.
2. It is possible to install the high efficiency filter on the SA face side of heat exchange element.
121109
158
High efficiency filter
(Optional accessory)
150~250
183
Inspection hole
416
247
850
Ceiling hook
4-12
X
40 oval hole
20
146
823
Supply air fan
(Maintenance cover)
416
800
Control box
132
137
879 132132
Maintenance cover
600~
Air filters
450
Heat exchange elements
Damper plate
137
68
123
306
(Control box)
20
Exhaust air fan
200
Maintenance space for the heat exchange
elements, the air filters and fans
247
SA
RA
OA
EA
Remark)
1. Be sure to provide the inspection hole (450
X
450 mm) to inspect the air filters, the exchange elements
and fans.
2. It is possible to install the high efficiency filter on the SA face side of heat exchange element.
123
183
132
High efficiency filter
(Optional accessory)
Damper plate
850
Ceiling hook
4-12
X
40 oval hole
600~
132
800
84
416 137
879
(Control box)
20
183
(Maintenance cover)
68
416
Maintenance cover
Maintenance space for the heat exchange
elements, the air filters and fans
Supply air fan
197
Air filters
Control box
306
137
450
247
84
123
247
213
150~250
20
823
Heat exchange elements
Exhaust air fan
Inspection hole
SA
RA
OA
EA
Remark)
1. Be sure to provide the inspection hole (450
X
450 mm) to inspect the air filters, the exchange elements
and fans.
2. It is possible to install the high efficiency filter on the SA face side of heat exchange element.
183
123 132
High efficiency filter
(Optional accessory)
137
338
162
193
600~
248
(Control box)
Damper plate
162
422
973
Ceiling hook
4-12
X
40 oval hole
Maintenance cover
Supply air fan
Heat exchange elements
150~250
196
Exhaust air fan
20
20
149
Inspection hole
Maintenance space for the heat exchange
elements, the air filters and fans
(Maintenance cover)
68
450
248
250
Control box
882
832
139
422
Air filters
137
897
SA
RA
OA
EA
Remark)
1. Be sure to provide the inspection hole (450
X
450 mm) to inspect the air filters, the exchange elements
and fans.
2. It is possible to install the high efficiency filter on the SA face side of heat exchange element.
139
193
149
Ceiling hook
4-12
X
40 oval hole
387
89
Maintenance space for the heat exchange
elements, the air filters and fans
Supply air fan
263
Heat exchange elements
High efficiency filter
(Optional accessory)
246
431
1110
Control box
600~
248
431
(Control box)
Maintenance cover
(Maintenance cover)
2020
832
248
150~250
Exhaust air fan
153
89
68
235
153
1034
Air filters
882
163
Damper plate
153
450
Inspection hole
SA
RA
OA
EA
Remark)
1. Be sure to provide the inspection hole (450
X
450 mm) to inspect the air filters, the exchange elements
and fans.
2. It is possible to install the high efficiency filter on the SA face side of heat exchange element.
235
163 153
50Hz,220–240V
60Hz,220V
100
300
0
400
500
200
External static pressure (Pa)
50
90
60
80
70
Exchange efficiency
(%)
60
90
60m
100
70
50Hz,220–240V
40m
0
200
200 400 600 800 1000 1200
20m
80m
60Hz,220V
100m
300
500
400
80
External static pressure (Pa)
250
Pipe
length
Exchange efficiency
(%)
Air flow rate
(m
3
/h)
Low
High
Temperatu
re
exchange efficienc
y
Enthalpy e
xchange
efficienc
y
(heating)
Enthalpy exchange efficiency
(c
ooling)
Ultra-High
VAM1000GJVE VAM2000GJVE
VAM1500GJVE
50Hz,220–240V
60
70
Low
60Hz,220V
50
25001500 2000500 1000
80
90
Temperature exch
a
nge efficiency
Enthalpy exchan
ge
efficiency (heatin
g)
Enthalpy
ex
ch
a
nge e
ff
ic
iency
(
c
o
ol
ing
)
300
500
0
600
700
400
100
200
External static pressure (Pa)
Exchange efficiency
(%)
Air flow rate
(m
3
/h)
25001500 2000500 1000
Air flow rate
(m
3
/h)
High
Ultra-High
Tempe
ra
ture e
x
change effic
ienc
y
Enthalpy exchange e
f
fi
c
ie
n
cy
(he
at
ing)
Enthalpy exchan
g
e efficien
c
y (
c
oo
ling)
Ultra-High
High
Low
Содержание
- Ask a qualified installer or contractor to install this product do not try to install the product yourself improper installation can result in water or refrigerant leakage electrical shock fire or explosion 1
- Cautions on product corrosion 1
- For any inquiries contact your local distributor 1
- Heat reclaim v entilation 1
- Pch0601 1
- Read the user s manual carefully before using this product the user s manual provides important safety instructions and warnings be sure to follow these instructions and warnings 1
- Use only those parts and accessories supplied or specified by daikin ask a qualified installer or contractor to install those parts and accessories use of unauthorized parts and accessories or improper installation of parts and accessories can result in water or refrigerant leakage electrical shock fire or explosion 1
- E nvironm e nt by inte rloc k ing w ith the a ir c onditione r 2
- Interlocking interlocking 2
- On off signal cooling heating mode signal set temperature signal ventilation signal humidifier on off signal 2
- Operating mode signal filter cleaning signal failure detection signal 2
- T he h r v c re a te s a h igh qua lity 2
- V a m g j s e rie s r e le a s e d 2
- Approx 3
- C entra lized c ontrol of air c onditioning a nd v entila tion 3
- F e a ture s of da ik in h r v 3
- Previous element fa model ultra thin film element 3
- V a m g j s e rie s 3
- 15 cdb 4
- Air conditioning load reduced by approximately 30 air conditioning load reduced by approximately 30 4
- Annual air conditioning 4
- Automatically switches the ventilation mode total heat exchange mode bypass mode according to the operating status of the air conditioner 4
- Bypass mode 4
- Cold climate compatible cold climate compatible 4
- Compact equipment compact equipment 4
- In comparison with normal ventilation fans 4
- Interlocking interlocking 4
- Load reduced by 4
- On off signal cooling heating mode signal set temperature signal ventilation signal humidifier on off signal 4
- Operating mode signal filter cleaning signal failure detection signal 4
- Reduces air conditioning load by not running the hrv while air is still clean soon after the air conditioner is turned on 4
- Standard operation at temperatures down to 15 c 4
- The hrv is interlocked to daikin s vrv system skyair and other air conditioning systems and automatically switches over ventilation mode further increasing the effects of energy conservation hrv operation has been centralized on the air conditioner remote controller allowing total control over air conditioning and ventilation with a simple configuration 4
- The intermittent operation mode is activated when outdoor temperature goes down to 10 c or below preventing freezing or condensation in the unit standard models can now be used in cold climate regions 4
- Total heat exchange mode 4
- With a height of just 306 mm the unit easily fits in limited spaces such as above ceilings 4
- A variety of control systems that can be controlled using only the air conditioner remote controller a variety of control systems that can be controlled using only the air conditioner remote controller 5
- C entra lized c ontrol of air c onditioning a nd v entila tion 5
- Centralized control system centralized control system 5
- Centralized controller 5
- Control with 2 remote controllers for hrv and air conditioner 5
- Group control 5
- Long distance remote control 5
- Operations and control with the air conditioning remote controller operations and control with the air conditioning remote controller 5
- Remote controller control 5
- Schedule timer 5
- The operation of the air conditioner using the remote controller is interlocked to the operation of the hrv greatly simplifying overall system operation in addition installation work associated with the hrv remote controller is not necessary because operations for air conditioning and ventilation are completely centralized on the air conditioner remote controller also the use of such a centralized remote controller allows the user to choose a wide range of control systems that integrate air conditioning and ventilation furthermore by using a variety of centralized control equipment the user can build a large high grade centralized control system 5
- Unified on off controller 5
- Air conditioners 6
- Air conditioning interlocked centralized control system 6
- Air conditioning interlocked control vrv skyair system 6
- Batch individual control system zone control system 6
- Centralized controller has setting and monitoring functions equivalent to those of a remote controller and can centrally control up to 128 vrv skyair and hrv units 6
- Combination with 6
- Connection adaptor no voltage a contact signal 6
- Hrv remote controller does not have to be used 6
- Independent 6
- Independent operation system 6
- Major hrv control systems 6
- Necessary accessories 6
- Operation 6
- Operation system 6
- Other types of 6
- Standard system multiple groups interlocked 6
- System characteristics 6
- System construction 6
- System without air conditioner and hrv remote controllers can be constructed 6
- Unified on off controller vrv remote controller skyair remote controller when necessary centralized controller schedule timer hrv remote controller and skyair connection adaptor 6
- V a rious c ontrol s ys te m s a c c ording to a pplic a tions a nd c onditions 6
- A sign is displayed on the remote controller when the air filter needs cleaning 7
- Access door 7
- Fresh up operation 7
- Maintenance cover 7
- Model l ine u p 7
- Preventing dust from falling with directly mounted ducts 7
- Sick room floor area 7
- Simple design and construction 7
- Switch box 7
- The unit can be installed upside down in accordance with the conditions of the location 7
- Vam gjve series vam gjve series 7
- With only one 450 mm square inspection aperture maintenance and heat exchange element replacement can be performed with ease 7
- Air filters 8
- And fans 8
- Ceiling hook 4 1 8
- Control box 8
- Control box ceiling hook 4 1 8
- Damper plate 8
- Dimensions dimensions 8
- Enthalpy exchange efficiency cooling 8
- Enthalpy exchange efficiency heating 8
- Exhaust air fan 8
- Heat exchange elements 8
- High efficiency filter optional accessory 8
- Inspection hole 8
- It is possible to install the high efficiency filter on the sa face side of heat exchange element 8
- Maintenance cover 8
- Maintenance space for the heat exchange elements the air filters and fans 8
- Mm to inspect the air filters the exchange elements 8
- Oval hole 8
- Remark 1 be sure to provide the inspection hole 45 8
- Supply air fan 8
- Temperature exchange efficiency 8
- Vam gjve series vam gjve series 8
- Vam1000gjve vam1500gjve vam2000gjve 8
- Vam150gjve 8
- Vam250gjve 8
- Vam350gjve vam500gjve 8
- Vam650gjve vam800gjve 8
- Models 9
- S pec ific a tions 9
- Vam1000gjve 9
- Vam1500gjve 9
- Vam150gjve vam250gjve vam350gjve vam500gjve 9
- Vam2000gjve 9
- Vam650gjve vam800gjv 9
- Installation of optional products installation of optional product 10
- Option 10
- Option list 10
- Pc board adaptor for heater control kit 10
Похожие устройства
- Interstep SP-206T (IS-SP-206TUSBB0-000B201) Руководство пользователя
- Inter-Step SP-206T (IS-SP-206TUSBB0-000B201) Руководство пользователя
- HTC Touch Diamond 2 Краткое руководство
- HTC Touch Diamond 2 Руководство пользователя
- Daikin VAM350FC Инструкция по эксплуатации
- Daikin VAM350FC Технические данные
- Daikin VAM500FC Инструкция по эксплуатации
- Daikin VAM500FC Технические данные
- Daikin VAM650FC Инструкция по эксплуатации
- Daikin VAM650FC Технические данные
- Daikin VAM800FC Инструкция по эксплуатации
- Daikin VAM800FC Технические данные
- Daikin VAM1000FC Инструкция по эксплуатации
- Daikin VAM1000FC Технические данные
- Daikin VAM1500FC Инструкция по эксплуатации
- Daikin VAM1500FC Технические данные
- Daikin VAM2000FC Инструкция по эксплуатации
- Daikin VAM2000FC Технические данные
- Daikin VAM150FCVE Инструкция по эксплуатации
- Daikin VAM150FCVE Технические данные