6 Commissioning
Installation manual
19
EHVZ04~16S18CB3V
Daikin Altherma – Low temperature split
4P401672-1E – 2018.02
6 Commissioning
NOTICE
NEVER operate the unit without thermistors and/or
pressure sensors/switches. Burning of the compressor
might result.
6.1 Checklist before commissioning
Do NOT operate the system before the following checks are OK:
You read the complete installation instructions, as
described in the installer reference guide.
The indoor unit is properly mounted.
The outdoor unit is properly mounted.
The following field wiring has been carried out according
to this document and the applicable legislation:
▪ Between the local supply panel and the outdoor unit
▪ Between indoor unit and outdoor unit
▪ Between the local supply panel and the indoor unit
▪ Between the indoor unit and the valves (if applicable)
▪ Between the indoor unit and the room thermostat (if
applicable)
The system is properly earthed and the earth terminals
are tightened.
The fuses or locally installed protection devices are
installed according to this document, and have NOT been
bypassed.
The power supply voltage matches the voltage on the
identification label of the unit.
There are NO loose connections or damaged electrical
components in the switchbox.
There are NO damaged components or squeezed
pipes on the inside of the indoor and outdoor units.
Backup heater circuit breaker F1B on the switchbox is
turned ON.
There are NO refrigerant leaks.
The refrigerant pipes (gas and liquid) are thermally
insulated.
The correct pipe size is installed and the pipes are
properly insulated.
There is NO water leak inside the indoor unit.
The shut-off valves are properly installed and fully open.
The stop valves (gas and liquid) on the outdoor unit are
fully open.
The air purge valve is open (at least 2 turns).
The pressure relief valve purges water when opened.
The minimum water volume is guaranteed in all
conditions. See "To check the water volume" in
"3.2Preparing water piping"on page4.
The safety thermostat is connected.
INFORMATION
The software is equipped with an "installer-on-site" mode
([4‑0E]), that disables automatic operation by the unit. At
first installation, setting [4‑0E] is by default set to "1",
meaning automatic operation is disabled. All protective
functions are then disabled. If the user interface home
pages are off, the unit will NOT operate automatically. To
enable automatic operation and the protective functions,
set [4‑0E] to "0".
36 hours after the first power-on, the unit will automatically
set [4‑0E] to "0", ending "installer-on-site" mode and
enabling the protective functions. If – after first
installation – the installer returns to the site, the installer
has to set [4‑0E] to "1" manually.
6.2 Checklist during commissioning
The minimum flow rate during backup heater/defrost
operation is guaranteed in all conditions. See "To check
the water volume and flow rate" in "3.2 Preparing water
piping"on page4.
To perform an air purge.
To perform a test run.
To perform an actuator test run.
Underfloor screed dryout function
The underfloor screed dryout function is started (if
necessary).
6.2.1 To check the minimum flow rate
Mandatory procedure for the additional zone
1 Confirm according to the hydraulic configuration which space
heating loops can be closed due to mechanical, electronic, or
other valves.
2 Close all space heating loops that can be closed (see previous
step).
3 Start the pump test run operation (see "6.2.4 To perform an
actuator test run"on page20).
4 Go to [6.1.8]: > Information > Sensor information > Flow rate
to check the flow rate. During pump test run operation, the unit
can operate below this minimum required flow rate that is
needed during defrost/backup heater operation.
Bypass valve foreseen?
Yes No
Modify the bypass valve setting
to reach the minimum required
flow rate + 2l/min
In case the actual flow rate is
below the minimum flow rate
(required during defrost/backup
heater operation), modifications
at hydraulic configuration are
required. Increase the space
heating loops that can NOT be
closed or install a pressure
controlled bypass valve.
Recommended procedure for the main zone
5 Confirm according to the hydraulic configuration which space
heating loops can be closed due to mechanical, electronic, or
other valves.
6 Close all space heating loops that can be closed (see previous
step).
7 Create a thermo request on the main zone only.
8 Wait 1 minute until the unit is stabilized.
Содержание
- Daikin altherma low temperature split 1
- Ehvz04s18cb ehvz08s18cb ehvz16s18cb 1
- Installation manual 1
- 551 qua emc 2
- Daikin europe n v 2
- Daikin tcf 25h4 01 2015 2
- Dekra nb0344 2
- Director 2
- Ehvz04s18cb3v ehvz08s18cb3v ehvz16s18cb3v 2
- Electromagnetic compatibility 2014 30 eu 2
- En60335 2 40 2
- Installation manual 2
- Low voltage 2014 35 eu 2
- Ostend 1st of april 2016 2
- P384987 5f 2
- Shigeki morita 2
- A subset of the latest technical data is available on the regional 3
- About the box 3
- About the box 3 3
- About the documentation 3
- About the documentation 3 3
- About this document 3
- Addendum book for optional equipment 3
- Additional info about how to install optional equipment 3
- And manuals product information 3
- Authorised installers 3
- Commissioning 19 3
- Configuration 12 3
- Daikin website publicly accessible 3
- Documentation set 3
- Extranet authentication required 3
- Format digital files on http www daikineurope com support 3
- Format paper in the box of the indoor unit 3
- Format paper in the box of the indoor unit digital files on 3
- Format paper in the box of the outdoor unit 3
- General safety precautions 3
- Hand over to the user 21 3
- Http www daikineurope com support and manuals product information 3
- Indoor unit 3
- Indoor unit installation manual 3
- Installation 5 3
- Installation instructions 3
- Installer reference guide 3
- Latest revisions of the supplied documentation may be available on the regional daikin website or via your dealer 3
- Outdoor unit installation manual 3
- Preparation 4 3
- Preparation of the installation good practices reference data 3
- Remove the screws at the top of the unit 3
- Remove the top panel 3
- Safety instructions that you must read before installing 3
- Table of contents 3
- Target audience 3
- Technical data 21 3
- Technical engineering data 3
- The full set of latest technical data is available on the daikin 3
- The original documentation is written in english all other languages are translations 3
- This document is part of a documentation set the complete set consists of 3
- To remove the accessories from the indoor unit 3
- Installation site requirements of the indoor unit 4
- Preparation 4
- Preparing the installation site 4
- Preparing water piping 4
- To check the water volume and flow rate 4
- Installation 5
- Opening the units 5
- Overview of electrical connections for external and internal actuators 5
- Preparing electrical wiring 5
- To open the indoor unit 5
- Connecting the refrigerant piping 6
- Connecting the water piping 6
- Installation 6
- Mounting the indoor unit 6
- To connect the refrigerant piping to the indoor unit 6
- To connect the water piping 6
- To install the indoor unit 6
- To open the switch box cover of the indoor unit 6
- F a c e d b 7
- Installation 7
- To connect the recirculation piping 7
- To fill the domestic hot water tank 7
- To fill the water circuit 7
- About electrical compliance 8
- Connecting the electrical wiring 8
- Installation 8
- To connect the electrical wiring on the indoor unit 8
- To connect the main power supply 8
- To insulate the water piping 8
- Installation 9
- To connect the backup heater power supply 9
- To connect the user interface 9
- Installation 10
- To connect the electrical meters 10
- To connect the shut off valve 10
- Connect the alarm output cable to the appropriate terminals as shown in the illustration below 11
- Connect the changeover to external heat source cable to the appropriate terminals as shown in the illustration below 11
- Connect the domestic hot water pump cable to the appropriate terminals as shown in the illustration below 11
- Connect the power consumption digital inputs cable to the appropriate terminals as shown in the illustration below 11
- Connect the safety thermostat normal closed cable to the appropriate terminals as shown in the illustration below 11
- Fix the cable with cable ties to the cable tie mountings 11
- Installation 11
- Main zone 11
- To connect the alarm output 11
- To connect the changeover to external heat source 11
- To connect the domestic hot water pump 11
- To connect the power consumption digital inputs 11
- To connect the safety thermostat normal closed contact 11
- Configuration 12
- Finishing the indoor unit installation 12
- Overview configuration 12
- To close the indoor unit 12
- To fix the user interface cover to the indoor unit 12
- 00 04 08 0c 13
- 01 05 09 0d 13
- 03 07 0b 0f 13
- 06 0a 0e 13
- Basic configuration 13
- Cancel ok 13
- Configuration 13
- Quick wizard language time and date 13
- To access the most used commands 13
- Configuration 14
- Quick wizard options 14
- Quick wizard standard 14
- Configuration 15
- Quick wizard capacities energy metering 15
- Configuration 16
- Space heating control 16
- Configuration 17
- Contact helpdesk number 17
- Domestic hot water control 17
- Configuration 18
- Daikin altherma low temperature split 18
- Depending on the selected installer settings and unit type settings will be visible invisible 18
- Ehvz04 16s18cb3v 18
- Information 18
- Installation manual 18
- Menu structure overview installer settings 18
- P401672 1e 2018 2 18
- Checklist before commissioning 19
- Checklist during commissioning 19
- Commissioning 19
- To check the minimum flow rate 19
- Commissioning 20
- Possible actuator test runs 20
- To perform a test run 20
- To perform an actuator test run 20
- To perform an air purge 20
- To perform an underfloor heating screed dryout 20
- 11 24 28 21
- D096028 1a 21
- Hand over to the user 21
- Piping diagram indoor unit 21
- Refrigerant side water side 21
- Technical data 21
- Technical data 22
- Technical data 23
- Wiring diagram indoor unit 23
- Technical data 24
- Communication 25
- Core 3 core 25
- Core 3m included 25
- Core signal 25
- D096036a 25
- Electrical connection diagram for more details please check the unit wiring 25
- External room thermostat heat pump convector main and or additional zone optional part 25
- Field supply 25
- Optional part 25
- Or 3 core 25
- Signal 25
- Standard part 25
- Standard part power supply 25
- Technical data 25
- Way valve 25
- X0 5 2 core 25
Похожие устройства
- Daikin EHVZ16S18CB3V Таблица настроек полей
- Daikin EHVZ16S18CB3V Инструкция по эксплуатации
- Daikin EHBH04DA6V Технические данные
- Daikin EHBH04DA6V Инструкция по монтажу
- Daikin EHBH04DA6V Приложение к руководству для дополнительного оборудования
- MSI B450 GAMING PRO CARBON MAX WIFI Краткое Руководство
- Daikin EHBH04DA6V Руководство по монтажу
- Daikin EHBH04DA6V7 Технические данные
- Daikin EHBH04DA6V7 Инструкция по монтажу
- Daikin EHBH04DA6V Инструкция по эксплуатации
- Daikin EHBH04DA6V Руководство для установщика
- Daikin EHBH08DA6V7 Технические данные
- Daikin EHBH08DA6V7 Инструкция по монтажу
- Daikin EHBH04DA6V7 Приложение к руководству для дополнительного оборудования
- Daikin EHBH04DA6V Общие меры безопасности
- Daikin EHBH04DA6V7 Руководство по монтажу
- Daikin EHBH04DA6V Руководство по применению для пользователя
- Daikin EHBH08DA6V7 Приложение к руководству для дополнительного оборудования
- Daikin EHBH08DA6V7 Руководство по монтажу
- Daikin EHBH08DA6V Технические данные