Electric Characteristics ED12-321A
66 SUPER MULTI NX B-Series Cooling Only
Cooling (50Hz 240V)
3D039724#1
Combination
Units Power Supply Comp. OFM IFM
Hz Volts Min. Max. MCA MFA RLA W FLA W FLA
2.5
50 240 216 264
4.7
20
2.8
68 0.41
40 0.23
3.5 6.3 5.0 40 0.23
5.0 8.2 6.5 40 0.23
6.0 10.1 8.8 45 0.25
7.1 13.1 12.4 50 0.28
2.5+2.5 9.5 6.0 80 0.45
2.5+3.5 10.4 8.3 80 0.45
2.5+5.0 10.7 9.2 80 0.45
2.5+6.0 11.7 9.8 85 0.48
2.5+7.1 13.0 11.1 90 0.50
3.5+3.5 11.7 10.6 80 0.45
3.5+5.0 12.0 9.8 80 0.45
3.5+6.0 12.1 10.6 85 0.48
3.5+7.1 13.4 11.0 90 0.50
5.0+5.0 12.2 9.9 80 0.45
5.0+6.0 12.5 9.7 85 0.48
5.0+7.1 13.6 9.7 90 0.50
6.0+6.0 13.4 9.7 90 0.50
6.0+7.1 13.8 9.6 95 0.53
2.5+2.5+2.5 10.6 8.5 120 0.68
2.5+2.5+3.5 11.2 9.2 120 0.68
2.5+2.5+5.0 11.3 9.3 120 0.68
2.5+2.5+6.0 11.7 9.3 125 0.70
2.5+2.5+7.1 12.3 9.2 130 0.73
2.5+3.5+3.5 11.8 9.7 120 0.68
2.5+3.5+5.0 11.9 9.3 120 0.68
2.5+3.5+6.0 12.1 9.2 125 0.70
2.5+3.5+7.1 12.9 9.4 130 0.73
2.5+5.0+5.0 11.8 9.5 120 0.68
2.5+5.0+6.0 12.2 8.8 125 0.70
3.5+3.5+3.5 12.3 9.7 120 0.68
3.5+3.5+5.0 12.5 9.4 120 0.68
3.5+3.5+6.0 12.9 9.4 125 0.70
3.5+5.0+5.0 12.0 8.5 120 0.68
SYMBOLS: NOTES:
MCA : MIN. CIRCUIT AMPS (A) 1. RLA is based on the following conditions.
Power Supply: 50Hz 240V
Cooling
Indoor temp.: 27°CDB/19°CWB
Outdoor temp.: 35°CDB.
2. Maximum allowable voltage variation between phases is 2%.
3. Select wire size based on the value of MCA.
4. Instead of fuse, use circuit breaker.
MFA : MAX. FUSE AMPS (A)
RLA : RATED LOAD AMPS (A)
OFM : OUTDOOR FAN MOTOR
IFM : INDOOR FAN MOTOR
FLA : FULL LOAD AMPS (A)
W : FAN MOTOR RATED OUTPUT (W)