Daikin FWB11CTN [10/76] Rated technical data

Daikin FWB04CFN [10/76] Rated technical data
FWB
10
10 RATED TECHNICAL DATA
» 2 pipes
FWB 04 05 06 08
Speed min med max min med max min med max min med max
Declared speed 2,5,7 1,5,7 1,6,7 1,4,7
Rated air flow (E) m³/h 109 246 276 171 275 341 195 360 402 305 532 652
Available static pressure (E) Pa 10 50 63 19 50 77 19 50 63 17 50 75
Power input (E) W 24 57 82 34 69 106 34 85 106 76 143 192
Maximum current absorption A 0,40 0,56 0,56 1,10
Total cooling capacity (2)(E) kW 0,92 1,72 1,90 1,27 1,90 2,27 1,57 2,69 2,96 1,92 3,17 3,68
Sensible cooling capacity (2)(E) kW 0,61 1,21 1,34 0,89 1,34 1,59 1,07 1,86 2,03 1,42 2,39 2,81
FCEER class (E) D E
Water flow (1) l/h 160 306 340 222 339 408 274 476 527 343 568 664
Water pressure drop (1)(E) kPa 2 5 6 3 6 8 3 7 9 3 8 11
Heating capacity (3)(E) kW 0,88 1,81 1,99 1,33 1,98 2,35 1,59 2,80 3,10 2,35 3,71 4,31
FCCOP class (E) D
Water flow (3) l/h 153 315 346 231 345 408 276 488 538 408 644 749
Water pressure drop (3)(E) kPa 1 4 5 2 5 7 2 6 8 4 9 11
Standard coil - number of rows 3 3 4 3
Total sound power level (4) dB(A) 28 49 52 39 48 54 39 50 54 38 52 58
Inlet + radiated sound power level (4)(E) dB(A) 26 47 50 37 46 52 37 48 52 37 50 58
Outlet sound power level (4)(E) dB(A) 25 46 49 36 45 51 36 47 51 35 47 56
Water content - standard coil dm³ 1,20 1,20 2,20 1,60
FWB 10 11 15 17
Speed min med max min med max min med max min med max
Declared speed 1,6,7 1,6,7 5,6,7 5,6,7
Rated air flow (E) m³/h 333 687 760 333 687 760 1050 1163 1289 1050 1163 1289
Available static pressure (E) Pa 12 50 61 12 50 61 40 50 60 40 50 60
Power input (E) W 76 167 192 76 167 192 235 280 332 235 280 332
Maximum current absorption A 1,10 1,10 2,10 2,10
Total cooling capacity (2)(E) kW 2,22 4,22 4,63 2,44 4,79 5,23 6,15 6,66 7,21 6,91 7,49 8,12
Sensible cooling capacity (2)(E) kW 1,60 3,09 3,39 1,70 3,33 3,64 4,51 4,88 5,29 4,83 5,23 5,67
FCEER class (E) D
Water flow (1) l/h 394 753 828 432 850 930 1095 1191 1295 1225 1333 1448
Water pressure drop (1)(E) kPa 2 7 8 3 10 12 13 16 18 20 23 26
Heating capacity (3)(E) kW 2,54 4,76 5,17 2,63 5,03 5,49 6,68 7,22 7,80 7,18 7,80 8,46
FCCOP class (E) D
Water flow (3) l/h 442 827 898 457 875 955 1162 1256 1357 1248 1356 1472
Water pressure drop (3)(E) kPa 2 7 8 3 9 11 12 14 16 17 20 23
Standard coil - number of rows 3 4 3 4
Total sound power level (4) dB(A) 38 55 58 38 55 58 61 63 69 61 63 69
Inlet + radiated sound power level (4)(E) dB(A) 36 53 56 36 53 56 59 61 67 59 61 67
Outlet sound power level (4)(E) dB(A) 35 52 55 35 52 55 58 60 66 58 60 66
Water content - standard coil dm³ 2,50 3,30 2,50 3,30
(1) Water temperature 7°C / 12°C, air temperature dry bulb 27°C, wet bulb 19°C (47% relative humidity)
(2) Water temperature 7°C / 12°C, air temperature dry bulb 27°C, wet bulb 19°C (47% relative humidity) according to EN1397:2015
(3) Water temperature 45°C / 40°C, air temperature 20°C
(4) Sound power measured according to standards ISO 3741 and ISO 3742
(E) EUROVENT certified data
Power supply 230-1-50 (V-ph-Hz)