Daikin SB.RKXYQ5T8 [11/27] Capacity tables

Daikin SB.RKXYQ5T8 [11/27] Capacity tables
3
5
VRV Systems • SB.RKXYQ-T
9
Outdoor Unit • SB.RKXYQ-T
5 Capacity tables
5 - 2 Integrated Heating Capacity Correction Factor
SB.RKXYQ-T
The heating capacity tables do not take into account the capacity reduction in case of frost accumulation or defrost operation.
The capacity values that take these factors into account, or in other words, the integrated heating capacity values, can be calculated as follows:
Formula
A = Integrated heating capacity
B = Capacity characteristics value
C = Integrated correction factor for frost accumulation (see table)
A = B * C
Inlet air temperature of heat exchanger
-7/-7.6 -5/-5.6 -3/-3.7 0/-0.7 3/2.2 5/4.1 7/6
0,88 0,86 0,80 0,75 0,76 0,82 1,00
Notes
1. The figure shows the integrated heating capacity for a single cycle (from one defrost operation to the next).
[°CDB/°CWB]
5 HP
Defrost operation
Defrost operation
Time
1 cycle
Heating capacity
3D098840