Daikin SB.RKXYQ5T8 [6/27] Specifications

Daikin SB.RKXYQ5T8 [6/27] Specifications
Outdoor Unit • SB.RKXYQ-T
2
VRV Systems • SB.RKXYQ-T
4
2 Specifications
Notes
(1) Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 5m, level difference: 0m. Data for
standard efficiency series. Nominal air flow rate, ESP 30 Pa.
(2) Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m. Data for
standard efficiency series. Nominal air flow rate, ESP 30 Pa.
(3) Actual number of units depends on the indoor unit type (VRV DX indoor, etc.) and the connection ratio restriction for the system (being; 50% CR 130%).
(4) Refer to refrigerant pipe selection or installation manual
Sound power level is an absolute value that a sound generates. Nominal air flow rate, ESP 60 Pa.
Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to sound level drawings. Nominal air flow rate, ESP 60 Pa.
Sound values are measured in a semi-anechoic room.
For detailed contents of standard accessories, see installation/operation manual
RLA is based on following conditions: COOLING indoor temperature: 27°CDB / 19°CWB, outdoor temperature: 35°CDB. Nominal air flow rate, ESP 30 Pa.
MSC means the maximum current during start up of the compressor. VRV IV uses only inverter compressors. Starting current is always max. running current.
MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current.
MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker).
TOCA means the total value of each OC set.
FLA means the nominal running current of the fan
Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits.
Maximum allowable voltage range variation between phases is 2%.
Contains fluorinated greenhouse gases
2-3 Technical Specifications RKXYQ5T RDXYQ5T
Dimensions Unit Height mm 701 397
Width mm 600 1,456
Depth mm 554 1,044
Packed unit Height mm 838 1,245
Width mm 720 1,604
Depth mm 660 470
Weight Unit kg 77 97
Packed unit kg 86 117
Packing Material Carton
Weight kg 2.1 4.9
Packing 2 Material Wood
Weight kg 6.9 14.0
Packing 3 Material Plastic -
Weight kg 0.30 -
Casing Colour Daikin White Unpainted
Material Painted galvanized steel plate Galvanised steel
Heat exchanger Type - Cross fin coil
Fin Treatment - Anti-corrosion treatment (PE)
Compressor Quantity 1 -
Type Hermetically sealed swing inverter compressor -
Fan Type - Centrifugal
Quantity - 2
Air flow rate Cooling Nom. m³/min - 55
Discharge direction - Discharge duct
Fan motor Quantity - 2
Model - Brushless DC motor
Output W - 500
Sound pressure level Cooling Nom. dBA 47
Refrigerant Type R-410A
Charge kg 2 -