11 ■English
Wiring
WARNING
• Do not use tapped wires, stranded wires (CAUTION 1)), extension cords, or starburst connections, as they may cause over-
heating, electrical shock, or fire.
• Do not use locally purchased electrical parts inside the product. (Do not branch the power for the drain pump, etc., from the
terminal block.) Doing so may cause electric shock or fire.
• Be sure to install an earth leakage breaker. (One that can handle higher harmonics.)
(This unit uses an inverter, which means that it must be used an earth leakage breaker capable handling harmonics in order to
prevent malfunctioning of the earth leakage breaker itself.)
• Use an all-pole disconnection type breaker with at least 3mm between the contact point gaps.
• Do not connect the power wire to the indoor unit. Doing so may cause electric shock or fire.
• Do not turn on the safety breaker until all work is completed.
1) Strip the insulation from the wire (20mm).
2) Connect the inter-unit wires between the indoor and out-
door units so that the terminal numbers match.
Tighten the terminal screws securely. We recommend a
flathead screwdriver be used to tighten the screws. The
screws are packed with the terminal block.
CAUTION
• When connecting the inter-unit wire to the terminal block using
a single core wire, be sure to perform curling.
Problems with the work may cause heat and fires.
• If the stranded wires must be used, make
sure to use the round crimp-style terminal
for connection to the power supply terminal
block. Place the round crimp-style terminals
on the wires up to the covered part and
secure in place.
3) Pull the wire and make sure that it does not disconnect. Then fix the wire in place with a wire retainer.
Room
A
Room A
Room
B
Outdoor unit
Indoor unit
Be sure to use the dedicated circuits.
Safety breaker
Earth leakage
circuit breaker
50Hz
220-240V
To room B
Inter-unit wire
4-core 1.5mm² or more
H05RN
Power supply wire
3-core 2.5mm² or more
H05RN
Stranded wire
Round crimp-style
terminal
Good Wrong Good Wrong
1 2 3
LN
1 2 3
Make sure connecting the
piping and connecting
wiring fit into .
(Incorrect handling will
make it hard to attach the
stop valve cover, causing
deformation.)
ROOM-A
ROOM-B
A
B
A
B
Piping
Piping
Wiring
Wiring
Outdoor
unit
ROOM-A
ROOM-B
Piping
Piping
Wiring
Wiring
Outdoor
unit
Make absolutely sure all wiring is correct.
Make sure the wiring and piping from the indoor unit to the outdoor unit match.
4
4
P
Good Wrong
Shape wires so that the stop
valve cover fit securely.
Firmly secure wire retainer
so wire terminations will not
receive external stress.
Also use the two screws
located at the bottom of
the packing case to tighten
the four locations.
Power supply
ROOM-A
ROOM-B
Use the
specified wire
type and
connect it
securely.
Be sure to clamp the wire for
power source on this location.
ROOM-A
ROOM-B
Liquid piping
Gas piping
Liquid piping
Gas piping
Wire retainer
Refer to the figure.
Make sure the electrical
wiring does not come into
contact with the gas piping.
01_EN_3P210724-1F.fm Page 11 Tuesday, October 30, 2012 10:39 AM
Содержание
- Installation manual 1
- Models 1
- Mxs40g2v1b 2mks40g2v1b 2mxs40h2v1b 2mks40h2v1b 2mxs40h3v1b 2mks50g2v1b 2mxs50g2v1b 2mks50h2v1b 2mxs50h2v1b 2mxs50h3v1b 2amx40f2v1b 2amx40g2v1b 2amx40g3v1b 2amx50f2v1b 2amx50g2v1b 2amx50g3v1b 1
- R410a split series 1
- Umeda center bldg 2 4 12 nakazaki nishi kita ku osaka 530 8323 japan 2
- Caution 5
- English 5
- Safety precautions 5
- Warning 5
- Accessories 6
- Caution 6
- English 2 6
- Precautions for selecting the location 6
- Also insulate the connection on the outdoor unit 7
- Caution 7
- Clamping material 7
- English 7
- Indoor outdoor unit installation drawings 7
- Indoor outdoor unitinstallation drawings 7
- Insulation tube 7
- Service lid tape 7
- Use tape or insulating material on all connections to prevent air from getting in between the copper piping and the insulation tube be sure to do this if the outdoor unit is installed above 7
- Connections connection port 8
- English 4 8
- How to use reducers 8
- Installation 8
- Precautions on installation 8
- English 9
- If the outdoor unit is positioned higher than the indoor units if the outdoor unit is positioned otherwise if lower than one or more indoor units 9
- Outdoor unit installation guideline 9
- Piping to each indoor unit 20m max 9
- Selecting a location for installation of the indoor units 9
- Selecting a location for installation ofthe indoor units 9
- The maximum allowable length of refrigerant piping and the maximum allowable height difference between the outdoor and indoor units are listed below the shorter the refrigerant piping the better the performance connect so that the piping is as short as possible shortest allow able length per room is 3m 9
- Total length of piping between all units 30m max 9
- Wall facing one side 9
- Walls facing three sides 9
- Walls facing two sides 9
- Where a wall or other obstacle is in the path of outdoor unit s inlet or outlet airflow follow the installation guidelines below for any of the below installation patterns the wall height on the exhaust side should be 1200mm or less 9
- Caution 10
- Drain work only heat pump models 10
- Installing outdoor unit 10
- Refrigerant piping 10
- Refrigerant piping work 10
- Purging air and checking gas leakage 11
- Refrigerant piping work 11
- Warning 11
- Caution 12
- Charging with refrigerant 12
- Important information regarding the refrigerant used 12
- Refilling the refrigerant 12
- English 13
- Precautions for laying refrigerant piping 13
- Refrigerant piping work 13
- Warning 13
- Caution 14
- Forced cooling operation 14
- Pump down operation 14
- Caution 15
- English 15
- Good wrong good wrong 15
- Warning 15
- Wiring 15
- Caution 16
- English 12 16
- Maximum power input limitation setting 16
- Warning 16
- Caution 17
- Econo mode prohibition setting 17
- English 17
- Warning 17
- English 14 18
- Items to check 18
- Trial operation and testing 18
- P210724 1f m07b062f 19
Похожие устройства
- Daikin 2MXS40H2V1B Сервис мануал
- Daikin 2MXS40H3V1B Инструкция по монтажу
- Daikin 2MXS40H3V1B2 Инструкция по монтажу
- Daikin 2MXS50H2V1B Инструкция по монтажу
- Daikin 2MXS50H3V1B Инструкция по монтажу
- Daikin 2MXS50H2V1B Сервис мануал
- Daikin 2MXS50H3V1B2 Инструкция по монтажу
- Daikin 3MXM40N2V1B Руководство по эксплуатации
- Daikin 3MXM40N2V1B Инструкция по монтажу
- Daikin 3MXM40N2V1B Руководство по монтажу
- Daikin 3MXM52N2V1B Руководство по эксплуатации
- Daikin 3MXM52N2V1B Инструкция по монтажу
- Daikin 3MXM52N2V1B Справочное руководство для монтажника
- Daikin 3MXM68N2V1B Руководство по эксплуатации
- Daikin 3MXM40N2V1B Справочное руководство для монтажника
- Daikin 3MXM68N2V1B Инструкция по монтажу
- Daikin 3MXM52N2V1B Руководство по монтажу
- Daikin 3MXM68N2V1B Руководство по монтажу
- Daikin 3MXM68N2V1B Справочное руководство для монтажника
- Daikin 3MXM40N2V1B7 Справочное руководство для монтажника