Daikin 2MXS50H2V1B [94/289] Compressor protection function

Daikin ATXG50EV1B [94/289] Compressor protection function
Control Specification SiBE12-933_A
84 Function and Control
3.3.5 Compressor Protection Function
When turning the compressor from OFF to ON, the upper limit of frequency is set as follows.
(The function is not used when defrosting.)
40 class 50 class Unit
A 62 55
HzB 72 70
C 90 85
D 140 150
secondsE 180 180
F 300 300
(sec.)
Time
(R14042)
(Hz)
Frequency
C
B
A
DEF