Daikin FTXS35DVMW9 [112/205] Troubleshooting

Daikin FTKS35DVML [112/205] Troubleshooting
Troubleshooting SiEBE04-507
102 Service Diagnosis
Troubleshooting
Check No.5
Refer to P.121
Check No.6
Refer to P.122
Check No.11
Refer to P.124
Correct.
Reconnect.
Replace the four way valve
coil.
Replace the outdoor unit
PCB.
Reconnect in position.
Replace a defective
thermistor.
Refer to the refrigerant line
check procedure.
Replace the four way valve
(defective or dust-clogged).
(R3040)
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Four way valve coil
disconnected (loose)?
YES
YES
NO
Functioning
NO
Check No. 11
Check the refrigerant line.
Malfunctioning
Harness out of connector?
NO
YES
Disconnect the
harness from
the connector.
Resistance between
harnessesabout
3k±0.5k?
Malfunctioning
Functioning
Check No. 5
Check the four way valve
switching output.
YES
NO
Any thermistor disconnected?
Malfunctioning
Functioning
Check No. 6
Check the thermistors.
Check the continuity of the four
way valve coil and harness.
Insufficient gas
Water mixed
Stop valve defective