Daikin RXH25CAVMB [11/20] Capacity tables

Daikin RXH20CAVMB [11/20] Capacity tables
Outdoor Units • R-410A • RXH-CAVMB
5
Split Sky Air • Outdoor Units
10
5 Capacity tables
5 - 1 Cooling/Heating capacity tables
FTXS35C+ RXH35C
Cooling capacity 230V [50Hz]
AFR 7.7
BF 0.18
Indoor Outdoor temperature (°C)
EWB EDB 20 25 30 32 35 40
(°C) (°C) TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
14.0 20 2.93 2.14 0.78 2.84 2.07 0.87 2.74 2.00 0.96 2.69 1.97 0.98 2.62 1.92 1.00 2.51 1.84 1.08
16.0 22 3.17 2.31 0.80 3.06 2.24 0.89 2.96 2.16 0.98 2.91 2.12 1.00 2.83 2.07 1.02 2.72 1.98 1.10
18.0 25 3.40 2.49 0.81 3.29 2.40 0.90 3.18 2.32 1.00 3.13 2.28 1.01 3.04 2.22 1.04 2.92 2.13 1.12
19.0 27 3.52 2.57 0.82 3.41 2.49 0.91 3.29 2.40 1.01 3.23 2.36 1.02 3.15 2.30 1.05 3.02 2.20 1.13
22.0 30 3.89 2.84 0.84 3.76 2.75 0.94 3.63 2.65 1.04 3.57 2.61 1.05 3.48 2.54 1.08 3.33 2.43 1.16
24.0 32 4.14 3.02 0.86 4.00 2.92 0.96 3.86 2.82 1.06 3.80 2.77 1.07 3.70 2.70 1.10 3.55 2.59 1.19
Heating capacity 230V [50Hz]
AFR 8.1
Indoor Outdoor temperature (°CWB)
EDB -10 -5 0 6 10
(°C) TC PI TC PI TC PI TC PI TC PI
16.0 2.06 0.77 2.55 0.83 3.05 0.90 3.64 0.98 4.03 1.03
18.0 2.05 0.81 2.54 0.87 3.03 0.94 3.62 1.02 4.01 1.07
20.0 2.03 0.84 2.52 0.91 3.01 0.98 3.60 1.06 3.99 1.11
21.0 2.02 0.86 2.51 0.93 3.00 0.99 3.59 1.07 3.98 1.13
22.0 2.01 0.88 2.50 0.95 2.99 1.01 3.58 1.09 3.98 1.15
24.0 1.99 0.92 2.48 0.99 2.97 1.05 3.56 1.13 3.96 1.18
3D044307
SYMBOLS
AFR: Air flow rate (m
3
/min)
BF: Bypass factor
EWB: Entering wet bulb temp. (°CWB)
EDB: Entering dry bulb temp. (°CDB)
TC: Total capacity (kW)
SHC: Sensible heating capacity (kW)
PI: Power input (kW)
NOTES
1. Ratings shown are net capacities which include a deduction for indoor fan
motor heat
2. Shows nominal cooling capacities and power input
3. TC, PI and SHC must be calculated by interpolation using the figures in the
above tables. (Figures out of the tables should not be used for calculation.)
4. SHC is based on each EWB and EDB
SHC* = SHC correction for other dry bulb
SHC* = 0.02 x AFR (m
3
/min) x (1-BF) x (DB-EDB)
Add SHC* to SHC.
5. Capacities are based on following conditions:
Corresponding refrigerant piping length: 5 m
Level difference: 0 m
6. Air flow rate (AFR) and Bypass factor (BF) are taburated above.

Содержание

Похожие устройства

Скачать
Случайные обсуждения

Ответы 0

Здравствуйте. недавно этот кондиционер ушел в аварию. Пульт выдал 32 ошибки. Вскрыл внешний блок - там был только подгоревший диод на 15V, который успешно заменили. Вся остальная плата вроде прозванивается и живая. При установке обратно обнаружил, что катушка электромагнитного расширительного клапана при подключении к плате гасит сервисный индикатор на плате. при этом внутренний блок уходит в аварию и закрывает жалюзи. При отключении катушки - внутренний блок в аварию не уходит и индикатор на плате внешнего блока начинает мигать как положено. Собственно вопрос: Может ли умершая катушка вырубать плату на внешнем блоке, или проблема все таки в умершей плате наружного блока? Как определить? Если это все таки катушка - подойдет ли катушка от более современных блоков (на ней 5 проводов, а на моей - 6)?