Si04-703A Troubleshooting
Service Diagnosis 123
Troubleshooting
Check No.07
Refer to P.133
Check No.09
Refer to P.134
Note1: Refer to “1.3 Application of Silicon grease to a power transistor and a diode bridge” on P214.
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
(R8361)
NO
Slightly dirty
Malfunctioning
Too dirty
Functioning
NO
YES
Turn off the power and turn it on
again to get the system started.
Check the radiation fin
temperature.
Check No. 07
Check the installation condition.
NO
YES
YES
Radiation fin dirty?
Above 105˚C?
Check No. 09
Check the outdoor unit fan
or related.
Error displayed again?
Has PCB been replaced?
Check if the silicon grease
applied properly on the
radiation fin. If not, apply it
(
). (Note 1)
Check the power transistor
and fin for looseness. If they
are found to be fit tightly,
replace the PCB or the
power transistor.
Replace the outdoor unit
PCB.
Replace the fan motor.
Correct the connectors and
fan motor leads.
Clean up the radiation fin.
Silicon grease
Part No.: 1
172698