Daikin FTXS60FVLT [68/244] Forced operation mode

Daikin FTKS71FVM [68/244] Forced operation mode
Si04-703A Control Specification
Function and Control 57
Detail Judgment by Input Current
When an output frequency is exceeds 55 Hz (40Hz for 71-90 class) and the input current is less
than specified value, the adjustment is made for insufficient gas.
Judgment by Discharge Pipe Temperature
When discharge pipe temperature is 20~60°C (depending on the model or mode) higher than
target value and the electronic expansion value opening is 450~480 pulse (max.), the
adjustment is made for insufficient gas.
3.13 Forced Operation Mode
Outline Forced operating mode includes only forced cooling.
Detail Forced Cooling
3.14 Additional Function
3.14.1 POWERFUL Operation Mode
Compressor operating frequency is increased to PI Max. (Max. Hz of operating room) and
outdoor unit airflow rate is increased.
3.14.2 Voltage Detection Function
Power supply voltage is detected each time equipment operation starts.
Item Forced Cooling
Forced operation
allowing conditions
1) The outdoor unit is not abnormal and not in the 3-
minute stand-by mode.
2) The operating mode of the outdoor unit is the stop
mode.
3) The forced operation is ON.
The forced operation is allowed when the above “and”
conditions are met.
Starting/adjustment If the forced operation switch is pressed as the above
conditions are met.
1) Command
frequency
50/60 class : 66Hz (cooling)
71FVM(T) : 55Hz (cooling), 71-90FVMA : 31Hz
(cooling)
2) Electronic
expansion valve
opening
It depends on the capacity of the operating indoor
unit.
3) Outdoor unit
adjustment
Compressor is in operation
4) Indoor unit
adjustment
The command of forced operation is transmitted to
the indoor unit.
End 1) When the forced operation switch is pressed again.
2) The operation is to end automatically after 15 min.
Others The protect functions are prior to all others in the
forced operation.