Capacity Tables ED04-702
24 Room Air Conditioners F-Series
FTKS71FVM + RKS71FVM (50Hz 220-240V / 60Hz 220-230V)
3D056393
AFR 17.4
BF 0.30
INDOOR OUTDOOR TEMPERATURE(°CDB)
EWB EDB 20 25 30 32 35 40
°C °C TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
14.0 20 5.934.181.795.934.182.025.934.182.255.934.182.335.934.182.465.934.182.67
16.0 22 7.284.671.917.274.662.126.944.482.316.814.412.386.614.312.496.284.142.68
18.0 25 7.934.981.957.604.812.137.274.652.327.134.582.396.944.482.506.614.332.69
19.0 27 8.09 5.16 1.95 7.76 5.00 2.14 7.43 4.84 2.32 7.30 4.78 2.40
7.10 4.69 2.51 6.77 4.53 2.70
22.0 30 8.584.951.978.254.812.167.924.672.347.794.612.427.594.532.537.264.392.71
24.0 32 8.914.791.988.584.662.178.254.532.358.124.482.437.924.402.547.594.282.72
Symbols NOTE:
AFR : Air flow rate (m³/min.) 1. Capacities are based on the following conditions.
(1) Corresponding refrigerant piping length : 7.5m
(2) Level difference : 0m
2. shows nominal (rated) capacities and power input.
BF : Bypass factor
EWB : Entering wet bulb temp. C)
EDB : Entering dry bulb temp. (°C)
TC : Total capacity (kW)
SHC : Sensible heat capacity (kW)
PI : Power input (kW)