Daikin RKS60FVM [54/125] Installation guidelines

Daikin FTXS71FVMA [54/125] Installation guidelines
ED04-702 Installation Manual
Room Air Conditioners F-Series 53
Where a wall or other obstacle is in the path of outdoor unit’s intake or exhaust airflow, follow the
installation guidelines below.
For any of the below installation patterns, the wall height on the exhaust side should be 1200mm or less.
Outdoor Unit Installation Drawings
Installation Guidelines
(Foot bolt-hol
e
centres)
(Foot bolt-hole centres)
5
80
m
m
33
0
m
m
120mm
(From unit’
s side)
In sites with poor drainage,
use block bases for outdoor
unit.
Adjust foot height until the
unit is leveled. Otherwise,
water leakage or pooling of
water may occur.
Where there is a danger of
the unit falling, use foot bolts,
or wires.
Wrap the insulation
pipe with the finishing
tape from bottom to top.
CAUTION
Set the piping length
from 1.5m to 30m.
Service lid
Stop valve cover
Allow space for piping
and electrical servicing.
2
5
0m
m
fr
o
m
wa
ll
Unit: mm
More than 50 More than 50
Top view
More than 350
More
than 100
Walls facing two sides
Top view
More than
100
More than 50
Walls facing three sides
More
than 350
More than 100 More than 350
Side view
1200
or less
Wall facing one side
Max. allowable height
Max. allowable length
30m
20m
Min. allowable length
1.5m
Liquid pipe
Gas pipe
O.D. 6.4mm
O.D. 12.7mm
20g/m
Additional refrigerant
required for refrigerant
pipe exceeding 10m
in length.