Si04-703A Troubleshooting
Service Diagnosis 121
Troubleshooting
Check No.07
Refer to P.133
Check No.09
Refer to P.134
(R8286)
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
YES
NO
Slightly dirty
Malfunctioning
Too dirty
Functioning
NO
YES
WARNING
To cool down the electricals, the
outdoor unit fan gets started when
the radiation fin temperature rises
above 95˚C and stops itself when
it drops below 80˚C.
Turn off the power and turn it on
again.
Check the radiation fin
temperature.
Check No. 07
Check the installation condition.
Radiation fin dirty?
Above 95˚C?
Check No. 09
Check the outdoor unit fan
or related.
Error again or outdoor
unit fan activated?
Replace the outdoor unit
PCB.
Replace the outdoor unit
PCB.
Replace the fan motor.
Correct the connectors and
fan motor leads.
Clean up the radiation fin.