Daikin FHQ71BUV1B [94/340] L or ll operation for ffq bv1 only l for 4way outlet and ll for 2way or 3way outlet

Daikin FHQ100BUV1B [94/340] L or ll operation for ffq bv1 only l for 4way outlet and ll for 2way or 3way outlet
Si21-205A Indoor Unit
Function and Control 83
Fan and flap
operations
1: L or LL operation for FFQ-BV1 only.
(L for 4way outlet and LL for 2way or 3way outlet)
Fan Flap Remote
Controller
Indication
FHQ & FFQ
Heating
Operation
Hot Start from Defrost In Swing
Operation
OFF Horizontal Swing
In Airflow
Direction Setting
OFF Horizontal Set Position
Defrost In Swing
Operation
OFF Horizontal Swing
In Airflow
Direction Setting
OFF Horizontal Set Position
Thermostat OFF In Swing
Operation
LL Horizontal Swing
In Airflow
Direction Setting
LL Horizontal Set Position
Hot Start from
Thermostat OFF
(Cold Air Prevention)
In Swing
Operation
LL Horizontal Swing
In Airflow
Direction Setting
LL Horizontal Set Position
Stop (Error) In Swing
Operation
OFF Horizontal
In Airflow
Direction Setting
OFF Horizontal
Overload Thermostat
OFF
In Swing
Operation
LL Horizontal Swing
In Airflow
Direction Setting
LL Horizontal Set Position
Cooling
Operation
Thermostat ON in
Program Dry Mode
In Swing
Operation
LSwingSwing
In Airflow
Direction Setting
L Setting Set Position
Thermostat OFF in
Program Dry Mode
In Swing
Operation
OFF Swing Swing
In Airflow
Direction Setting
OFF Setting Set Position
Cooling Thermostat
OFF
In Swing
Operation
Setting Swing Swing
In Airflow
Direction Setting
Setting Setting Set Position
Stop (Error) In Swing
Operation
OFF Horizontal
In Airflow
Direction Setting
OFF Setting
Freeze Prevention in
Program Dry Mode
(Including Cooling
Operation)
In Swing
Operation
L
1
Swing Swing
In Airflow
Direction Setting
L
1
Setting Set Position